AC10 Inverter
Hazards
DANGER! - Ignoring the following may result in injury
1. This equipment can endanger life by
exposure to rotating machinery and high
voltages.
2. The equipment must be permanently
earthed due to the high earth leakage
current, and the drive motor must be
connected to an appropriate safety earth.
3. Ensure all incoming supplies are isolated
before working on the equipment. Be
aware that there may be more than one
supply connection to the drive.
4. There may still be dangerous voltages
present at power terminals (motor output,
supply input phases, DC bus and the
brake, where fitted) when the motor is at
standstill or is stopped.
5. For measurements use only a meter to
IEC 61010 (CAT III or higher). Always
begin using the highest range.
CAT I and CAT II meters must not be
used on this product.
6. Allow at least 5 minutes (20 minutes for
above 30kW) for the drive's capacitors
to discharge to safe voltage levels (less
than 50V). Use the specified meter
capable of measuring up to 1000V DC
& AC RMS to confirm that less than
50V is present between all power
terminals and ground.
7. Unless otherwise stated, this product
must NOT be dismantled. There are no
user-serviceable components. In the
event of a fault, the drive must be
returned to Parker. You will need
Return Material Authorization from your
local distributor.
WARNING! - Ignoring the following may result in injury or damage to equipment
SAFETY
Where there is conflict between EMC and Safety requirements, personnel safety shall
always take precedence.
Never perform high voltage resistance
checks on the wiring without first
disconnecting the drive from the circuit
being tested.
Ensuring ventilation is sufficient, provide
guarding and /or additional safety
systems to prevent injury or damage to
equipment.
When replacing a drive in an application
and before returning to use, it is
essential that all user defined
parameters for the product’s operation
are correctly installed.
The AC10 series is not a safety
component or safety related product.
All control and signal terminals are
SELV, i.e. protected by double
insulation. Ensure all external wiring is
rated for the highest system voltage.
Thermal sensors contained within the
motor must have at least basic
insulation.
All exposed metalwork in the Inverter is
protected by basic insulation and
bonded to a safety ground.
RCDs are not recommended for use
with this product but, where their use is
mandatory, only Type B RCDs should
be used.
EMC
In a domestic environment this product
may cause radio interference in which
case supplementary mitigation measures
may be required.
This equipment contains electrostatic
discharge (ESD) sensitive parts.
Observe static control precautions when
handling, installing and servicing this
product.
This is a product of the restricted sales
distribution class according to IEC
61800-3. It is designated as
“professional equipment” as defined in
EN61000-3-2. Permission of the supply
authority shall be obtained before
connection to the low voltage supply.
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...