8-8
AC10 Inverter
+
-
S1
V
J
J5
ii.
Press the “M” key, to enter the programming menu.
iii.
Study the parameters of the motor: the operation process is the same as that of
example 1. (Refer to 8.3.1 for tuning of the motor).
iv.
Set functional parameters of the inverter:
Frames 1
– 5 upto 22kW
v.
There is a red two-digit coding switch SW1 near the control terminal block, as
shown in Figure 8-4. The function of coding switch is to select the voltage signal
(0
~
5V/0
~
10V) or current signal of analog input terminal AI2, current channel is
default. In actual application, select the analog input channel through F203. Turn
switches 1 to ON and 2 to ON as illustrated in the figure, to select 0
~
20mA
current speed control.Other states and modes of these switches are shown in
table 8-2,
Frames 6
– 11 30kW – 150kW
vi.
There is a red four-digit coding switch SW1 near the control terminal blockr, as
shown in Figure 8-5. The function of coding switch is to select the input range (0
~
5V/0
~
10V/0~20mA) of analog input terminal AI1 and AI2. In actual application,
select the analog input channel through F203. AI1 channel default value is 0~10V,
AI2 channel default value is 0~20mA. Other states and modes of these switches
are shown in table 8-3.
vii.
There is a toggle switch S1 at the side of control terminals,refer to Fig 8-6. S1 is
used to select the voltage input range of AI1 channel. When turning S1 to “+”, the
input range is 0~10V, when turning S1 to “-”, the input range is -10~10V.
viii.
Close the switch DI3, the motor starts forward running;
ix.
The potentiometer can be adjusted and set during running, and the current setting
frequency of the inverter can be changed;
x.
During running process, switch off the switch DI3, then, close DI4, the running
direction of the motor will be changed;
xi.
Switch off the switches DI3 and DI4, the motor will decelerate until it stops running;
xii.
Switch off the main switch to power off the inverter.
xiii.
Analog output terminal AO1 can output voltage and current signal, the selecting
switch is J5, refer to Fig 8-7 the output relation is shown in Table 8-.4.
Figure 8-4
Figure 8-5
Figure 8-6
Figure 8-7
Function code
Parameter
Values
F203
Main frequency source
1
F208
Terminal operational mode
1
ON
2
1
SW1
SW1
ON
1
4
2
3
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...