8-7
AC10 Inverter
ii.
Press the “M” key, to enter the programming menu.
iii.
Study the parameters of the motor: the operation process is the same as that of
example 1. (Refer to 8.3.1 for tuning of the motor).
iv.
Set functional parameters of the inverter:
Function code
Parameter
Values
F124
Jogging frequency
5.00
F125
Jogging acceleration time
30
F126
Jogging deceleration time
30
F132
Display items for stop mode
1
F202
Direction setting mode
0
v.
Press and hold the “I” key until the motor is accelerated to the jogging frequency,
and maintain the status of jogging operation.
vi.
Release the “I” key, or until motor reaches 0 speed;
vii.
Switch off the main switch to power off the inverter.
8.3.4 Setting the frequency with analog terminal and controlling the operation with control
terminals
i.
Connect the wires in accordance with Figure 8-3. After having checked the wiring
successfully, switch on the mains supply, and power on the inverter. Note: 2K
~
5K
potentiometer may be used for setting external analog signals. For the cases with
higher requirements for precision, a precise multiturn potentiometer is
recommended, and adopt shielded wire for the wire connection, with near end of
the shielding layer grounded reliably.
Figure 8-3
Wiring Diagram 3
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...