3-1
AC10 Inverter
Chapter 3
Installation
IMPORTANT Read Chapter 14
“Compliance” before installing this unit.
3.1 Equipment Precautions
Check for signs of transit damage.
Check the product code on the rating label conforms to your requirements.
Installation and application environment should be free of rain, drips, steam, dust and oily
dirt; without corrosive or flammable gases or liquids, metal particles or metal powder.
Environment temperature within the scope of -10
℃
~
+50
℃ (40℃
without derating)
Ensure inverter is installed away from combustibles.
Do not drop anything into the inverter.
The reliability of inverters relies heavily on the temperature. As the surrounding
temperature increases by 10 degrees the inverter life will be halved.
The inverter is designed to be installed in a control cabinet. The inverter should be
mounted to allow free air flow. The inverter should be installed vertically on a solid, flat,
vertical surface. If there are several inverters in one cabinet, in order to ensure ventilation,
install inverters side by side. If it is necessary to install several inverters above each other,
you need additional ventilation.
Never touch the internal elements for 15 minutes after power goes off. Wait until it is
completely discharged. Use a meter capable of measuring up to 1500 VDC & 600 VAC
RMS to confirm that less than 50V is present on the DC BUS and between all power
terminals and earth before working on or near the DC Bus
Input terminals L1/R, L2/S and L3/T are connected to power supply of 400V/230V (L1, L2
are connected to 230V) while output terminals U, V and W are connected to motor.
Proper grounding should be ensured. Separate grounding is required for motor and
inverter. Grounding with series connection is forbidden.
There should be separate wiring between control loop and power loop to avoid any
possible interference.
Cable length should be minimized to limit common mode interference.
If circuit breaker or contactor needs to be connected between the drive and the motor, be
sure to operate these circuit breakers or contactor when the drive has no output, to avoid
damaging the drive.
Before using the drive, the insulation of the motors must be checked, especially if it is used for
the first time or if it has been stored for a long time. This is to reduce the risk of the drive being
damaged by poor insulation of the motor.
Do not connect any varistor or capacitor to the output terminals of the drive because the drive’s
output voltage waveform is pulse wave, otherwise tripping or damaging of components may
occur.
Ensure the installation complies with all local and national electrical codes.
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...