AC10 Inverter
F406 Lower limit of AI2 channel input (V) Setting range: 0.00
~
F408
Mfr’s value: 0.01
F407 Corresponding setting for lower limit
of AI2 input
Setting range: 0
~
F409
Mfr’s value: 1.00
F408 Upper limit of AI2 channel input (V) Setting range: F406
~
10.00 Mfr’s value: 10.00
F409 Corresponding setting for upper limit
of AI2 input
Setting range:
Max (1.00
,
F407)
~
2.00
Mfr’s value: 2.00
F410 AI2 channel proportional gain K2
Setting range: 0.0
~
10.0
Mfr’s value: 1.0
F411 AI2 filtering time constant (s)
Setting range: 0.1
~
50.0
Mfr’s value: 0.1
The function of AI2 is the same with AI1.
F418 AI1 channel 0Hz voltage dead zone
Setting range:
0
~
0.50V (Positive-Negative)
Mfr’s value: 0.00
F419 AI2 channel 0Hz voltage dead zone
Setting range:
0
~
0.50V (Positive-Negative)
Mfr’s value: 0.00
An analog input voltage 0-5V can correspond to output frequency -50Hz-50Hz (2.5V
corresponds to 0Hz) by setting the function of corresponding setting for upper / lower limit of
analog input. The function codes F418 and F419 set the voltage range corresponding to 0Hz.
For example, if F418=0.5 and F419=0.5, then the voltage range from (2.5-0.5 = 2) to (2.5+0.5 = 3)
corresponds to 0Hz. If the voltage is in the range of 2 to 3 volts, the inverter will output 0Hz.
0HZ voltage dead zone will be valid when corresponding setting for lower limit of input is less
than 1.00.
When F421 is set to 0, local keypad panel is working. When F421 is set to 1, remote control
keypad panel is working, and local keypad panel will be disabled for saving energy.
The remote control panel is connected by 8-conductor network cable (RJ45).
AC10 has one analog output channel (AO1) selectable for current or voltage output.
F423 AO1 output range
Setting range:
0: 0
~
5V;
1: 0
~
10V or 0~20mA
2: 4~20mA
Mfr’s value: 1
F424 AO1 lowest corresponding
frequency (Hz)
Setting range: 0.0
~
F425
Mfr’s value: 0.05
F425 AO1 highest corresponding
frequency (Hz)
Setting range: F424
~
F111
Mfr’s value: 50.00
F426 AO1 output compensation (%) Setting range: 0
~
120
Mfr’s value: 100
AO1 output range is selected by F423. When F423=0, AO1 output range selects 0-5V, and
when F423=1, AO1 output range selects 0-10V or 0-20mA. When F423=2, AO1 output range
selects 4-20mA (When AO1 output range selects current signal, please turn the switch J5 to “I”
position.
Correspondence of output voltage range (0-5V or 0-10V) to output frequency is set by F424
and F425. For example, when F423=0, F424=10 and F425=120, analog channel AO1 outputs
F421 Keypad
selection
Setting range:
0: Local keypad panel
1: Remote control keypad panel
2: local remote keypad
Mfr’s value: 1
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...