9-30
AC10 Inverter
F500 Stage speed type
Setting range:
0: 3-stage speed;
1: 15-stage speed;
2: Max 8-stage speed auto circulating
Mfr’s value: 1
In case of multi-stage speed control (F203=4), the user must select a mode by F500. When
F500=0, 3-stage speed is selected. When F500=1, 15-stage speed is selected. When F500=2,
max 8-stage speed auto circulating is selected. When F500=2, “auto circulating” is classified
into “2-stage speed auto circulating”, “3-stage speed auto circulating”, … “8-stage speed auto
circulating”, which is to be set by F501.
Table 9-6 Selection of Stage Speed Running Mode
F203
F500 Mode of Running
Description
4
0
3-stage speed control
The priority in turn is stage-1 speed, stage-2 speed
and stage-3 speed. 3-stage speed control can be
combined with analog speed control. If F207=4, “3-
stage speed control” is prior to analog speed
control.
4
1
15-stage speed control
15-stage speed control can be combined with
analog speed control. If F207=4, “15-stage speed
control” is prior to analog speed control.
4
2
Max 8-stage speed auto
circulating
Adjusting the running frequency manually is not
allowed. The number of speed control stages may be
selected via F501.
F501 Selection of Stage Speed
Under Auto-circulation Speed Control
Setting range: 2
~
8
Mfr’s value: 7
F502 Selection of number of cycles
of Auto-circulation Speed Control
Setting range: 0
~
9999
(when the value is set to 0, the
inverter will carry out infinite
circulating)
Mfr’s value: 0
F503 Status After Auto-circulation
Running Finished.
Setting range:
0: Stop
1: Keep running at last-stage speed
Mfr’s value: 0
If running mode is auto-circulation speed control (F203=4 and F500=2), please set the related
parameters by F501~F503 define the auto-circulation cycle characteristics.
The inverter runs at the preset stage speed one by one under the auto-circulation speed
control is called as cycle.
If F502=0,
inverter will run at infinite auto circulation, which will be stopped by “stop” signal.
If F502>0, inverter will run at auto circulation conditionally. When auto circulation of the preset
cycles is finished continuously (set by F502), inverter will finish auto-circulation running
conditionally. When inverter keeps running and the preset cycles is not finished, if inverter
receives “stop command”, inverter will stop. If inverter receives “run command” again, inverter
will automatically circulate by the setting time of F502.
If F503=0, then inverter will stop after auto circulation is finished. If F503=1, then inverter will
run at the speed of the last-stage after auto-circulation is finished as follows:
F501=3, the inverter will run 3-stage speed auto circulation
F502=100, the inverter will run 100 cycles of auto circulation
F503=1, the inverter will continue to run at the speed of the last stage after the number
of auto-circulation cycles is completed
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...