9-28
0-5V and the output frequency is 10-120Hz.
AO1 output compensation is set by F426. Analog excursion can be compensated by setting
F426.
F427 AO2 output range
Setting range:
0: 0
~
20mA;
1: 4
~
20 mA
Mfr’s value: 0
F428 AO2 lowest corresponding
frequency (Hz)
Setting range: 0.0
~
F429
Mfr’s value: 0.05
F429 AO2 highest corresponding
frequency (Hz)
Setting range: F428
~
F111
Mfr’s value: 50.00
F430 AO2 output compensation (%) Setting range: 0
~
120
Mfr’s value: 100
The function of AO2 is the same as AO1, but AO2 will output current signal, current signal of 0-
20mA and 4-20mA could be selected by F427.
F431 AO1 analog output signal
Setting range:
0: Running frequency;
1: Output current;
2: Output voltage;
3: Analog AI1;
4: Analog AI2;
6: Output torque;
7: Given by PC/PLC;
8: Target frequency
Mfr’s value: 0
F432 AO2 analog output signal
Mfr’s value: 1
When output current is selected, analog output signal is from 0 to twice rated current.
When output voltage is selected, analog output signal is from 0V to rated output voltage.
F433 Corresponding current for full
range of external voltmeter
Setting range:
0.01
~
5.00 times of rated current
Mfr’s value: 2.00
F434 Corresponding current for full
range of external ammeter
Mfr’s value: 2.00
In case of F431=1 and AO1 channel for token current, F433 is the ratio of measurement range
of external voltage type ammeter to rated current of the inverter.
In case of F432=1 and AO2 channel for token current, F434 is the ratio of measurement range
of external current type ammeter to rated current of the inverter.
For example: measurement range of external ammeter is 20A, and rated current of the inverter
is 8A, then, F433=20/8=2.50.
The greater the value of F437, the more stable the analog monitoring will be, but the slower
the response speed will be. Adjust the filter according to the actual system requirements.
F437 Analog filter width
Setting range: 1
~
100
Mfr’s value:10
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...