9-20
AC10 Inverter
F312 At Speed threshold
Setting range: 0.00
~
5.00Hz
Mfr’s value: 0.00
When F300=15 or F301=15, threshold range is set by F312.
For example: when F301=15, target frequency is 20HZ and F312=2, the running frequency
reaches 18Hz (20-2), ON signal is output by DO1 until the running frequency reaches target
frequency.
9.3.2 Digital multifunctional input terminals
F316 DI1 terminal function setting
Setting range:
0: no function
1: Run
2: Stop
3: Multi-stage speed terminal 1
4: Multi-stage speed terminal 2
5: Multi-stage speed terminal 3
6: Multi-stage speed terminal 4
7: Reset
8: Free stop
9: External coast stop
10: Acceleration/deceleration forbidden
11: Forward run jogging
12: Reverse run jogging
13: UP frequency increasing terminal
14: DOWN frequency decreasing terminal
15: “FWD” terminal
16: “REV” terminal
17: Three-line type input “X” terminal
18: Acceleration/deceleration 1
19: Reserved
20: Speed/torque switchover
21: Frequency source switchover
32: Fire control switchover
33: Emergency fire control
34: Accel / decel switchover 2
37: Common-open PTC heat protection
38: Common-close PTC heat protection
48: High-frequency switchover
52: Jogging (no direction)
53: Watchdog
54: Frequency reset
55: switchover between manual running and
auto running
56: Manual running
57: Auto running
58: Direction
Mfr’s value: 11
F317 DI2 terminal function setting
Mfr’s value: 9
F318 DI3 terminal function setting
Mfr’s value: 15
F319 DI4 terminal function setting
Mfr’s value: 16
F320 DI5 terminal function setting
Mfr’s value: 7
F321 DI6 terminal function setting
Mfr’s value: 8
F322 DI7 terminal function setting
Mfr’s value: 0
F323 DI8 terminal function setting
Mfr’s value: 0
This parameter is used for setting the corresponding function for multifunctional digital input
terminal.
Both free stop and external coast stop of the terminal have the highest priority.
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...