9-18
AC10 Inverter
Value Function
Instructions
11
Motor overload pre-alarm
After motor overloads, ON signal is output after the
half time of protection timed, ON signal stops
outputting after overload stops or overload
protection occurs.
12
Stalling
During accel/decel process, inverter stops
accelerating/decelerating because inverter is
stalling, and ON signal is output.
13
Inverter is ready to run
When inverter is powered on. Protection function
is not in action and inverter is ready to run, then
ON signal is output.
14
In running status 2
Indicating that inverter is running and ON signal is
output. When inverter is running at 0HZ, its seen as
the running status, and ON signal is output.
15
Frequency arrival output
At Speed
Indicating inverter runs at the setting target
frequency, and ON signal is output. See F312.
16
Overheat pre-alarm
Warning
When temperature reaches 80% of setting value,
the output is true until overheat protection occurs
or temperature is lower than 80% of setting
value, then the output becomes false.
17
Over latent current output
When output current of inverter reaches the
setting over latent current, ON signal is output.
See F310 and F311.
18
Analog line disconnection
protection
Indicating inverter detects analog input lines
disconnection, and ON signal is output refer to
F741.
19
Reserved
20
At zero output current
When inverter output current has fallen to zero
current detecting value, and the duration time
(F755) has elapsed the signal is true, reffer to
F754 and F755.
21
DO1 Output controlled by
PC/PLC
1 means output is True
0 means output is False.
22
Reserved
23
TA\TC Output controlled by
PC/PLC
24
Watchdog
The output is valid when inverter trips into Err6.
25-39 Reserved
40
Switchover of high-frequency
performance
When this function is valid, inverter will switch
into high-frequency optimizing mode.
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...