9-46
AC10 Inverter
FA58 Fire pressure given value (%)
Setting range:
0.0~100.0
Mfr’s value: 80.0
FA58 is also called second pressure, when the fire pressure switchover terminal is valid,
pressure target value will switch into second pressure value.
FA59 Emergency fire mode
Setting range:
0: Disabled
1: Emergency fire mode 1
2: Emergency fire mode 2
Mfr’s value: 0
When emergency fire mode is valid and emergency fire control terminal is valid, fire mode
controls are valid and inverter will run at the frequency of FA60 or target frequency until
inverter is broken. When OC and OE protection occur, inverter will reset automatically and
start running .
Emergency fire mode 1: when the terminal is valid, inverter will run at target frequency.
Emergency fire mode 2: when the terminal is valid, inverter will run at the frequency of FA60.
FA60 Running frequency of emergency fire Setting range:
F112~F111
Mfr’s value: 50.0
When the emergency fire mode 2 is valid and the emergency fire control terminal is valid,
inverter will run at the frequency set by FA60.
FA62 when emergency fire
control terminal is invalid
Setting range:
0: inverter can not be stopped manually
1: inverter can be stopped manually
Mfr’s value: 0
•FA62=0, when emergency fire control terminal (DIx=33) is invalid, before repower or inverter,
or reset inverter, inverter can not be stopped manually.
•FA62=1, when emergency fire control terminal (DIx=33) is invalid, after quitting from
emergency fire mode, inverter can be stopped manually
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...