INSTRUCTION MANUAL

HYBRID SOLAR INVERTER

INTRODUCTION

Thank you for selecting and buying V-TAC product. V-TAC will serve you the best. Please read these instruc-

tions carefully before starting the installation and keep this manual handy for future reference. If you have any 

another query, please contact our dealer or local vendor from whom you have purchased the product. They 

are trained and ready to serve you at the best. The warranty is valid for 5 years from the date of purchase. The 

warranty does not apply to damage caused by incorrect installation or abnormal wear and tear. The company 

gives no warranty against damage to any surface due to incorrect removal and installation of the product. 

This product is warranted for manufacturing defects only.

MULTI-LANGUAGE MANUAL QR CODE

Please scan the QR code to access the manual in 

multiple languages.

WEEE Number: 80133970

IN CASE OF ANY QUERY/ISSUE WITH THE PRODUCT, PLEASE REACH OUT TO US AT: [email protected]

FOR MORE PRODUCTS RANGE, INQUIRY PLEASE CONTACT OUR DISTRIBUTOR OR NEAREST

DEALERS. V-TAC EUROPE LTD. BULGARIA, PLOVDIV 4000, BUL.L.KARAVELOW 9B

PV INPUT PARAMETER

Mppt Input Voltage

550V

Vmax PV

550V

Max. Input Current

18.5x2A

lsc PV 

26x2A

AC INOUT/OUTOUT PARAMETER

Rated Apparent Power

3.6kVA

Rated Current

16.4/15.7A

Rated Voltage

198 to 

242@220/207 to 

253@230V

Rated Frequency

50/60Hz

Power Factor Range

1 (-0.8~+0.8 adjust-

able)

BATTERY PARAMETER

Storage type:

Li-ion / Lead-acid 

etc.

Battery input voltage:

40V-60V

Cut Off Voltage:

39.5V

Max. charging Voltage:

60V

Max. Protective Voltage:

62V

Max. continuous charging 

Current:

80A

Max.Discharging Current:

80A

SYSTEM

Protective Class:

Class I

Type of Isolation:

Transformerless

Ingress Protection:

IP65

Over Voltage Category:

II

Dimension(W*D*H):

513*370*192mm

Weight:

17kg

Max.Efficiency:

97.6%

MODEL

VT-6607136

SKU

11576

Summary of Contents for VT-6607136

Page 1: ...ode to access the manual in multiple languages WEEE Number 80133970 IN CASE OF ANY QUERY ISSUE WITH THE PRODUCT PLEASE REACH OUT TO US AT SUPPORT V TAC EU FOR MORE PRODUCTS RANGE INQUIRY PLEASE CONTAC...

Page 2: ...n delivery Pay attention to waterproof Do not expose the inverter directly to water rain snow or spray 7 Alternative uses modifications to the inverter not recommended The warranty can become void if...

Page 3: ...mode is for the regions with low feed in tariff and high electricity prices The energy produced by the PV system is used to optimize self consumption needs The excess energy is used to recharge the ba...

Page 4: ...de is designed to reward customers who do their part to reduce demand on the electric grid particularly during peak usage periods Use most of your electricity from PV energy and during off peak time p...

Page 5: ...eriods of time discharge setting the battery will be charged firstly The Selling First mode is suitable for the regions with high feed in tariff When the grid fails the system will automatically switc...

Page 6: ...ructions Warrenty Card Monitor Quick Installation Instructions No Qty Items No Qty Items 1 1 Hybrid Inverter 11 1 Grounding Terminal 2 1 Certificate Of Inspection 12 1 Wall Mounting Bracket 3 1 Quick...

Page 7: ...oduct Overview Inverter Terminals No Items No Items 1 DC Switch 5 Communication Port 2 DC Connectors For PV Strings 6 AC Port EPS Port 3 DC Connectors For PV Strings 7 Monitor Module Port 4 Battery Po...

Page 8: ...olid surface far from flammable or corrosion materials where is suitable for inverter s weight and dimensions The ambient temperature should be within 25 C 60 C between 13 F and 140 F The installation...

Page 9: ...Mounting STEP 1 STEP 2 Leave the enough space around inverter easy for accessing to the inverter connection points and maintenance...

Page 10: ...NTC Meter 485A 2 NTC Meter 485B 3 Dry Contact BAT 485A 4 Dry Contact BAT CANH 5 DRM BAT CANL 6 DRM BAT 485B 7 485A CTU 8 485B CTN Note For diesel generators or multi machine parallel use please contac...

Page 11: ...r other wise inverter could be damaged The open circuit voltage and short circuit current of PV string should not exceed the reasonable range of the inverters The isolation resistance between PV strin...

Page 12: ...stributor or VTAC for technical support Note Set battery type and manufacturer please refer to Chapter 5 3 BMS Battery Management System communication is needed between inverter and battery Pass the c...

Page 13: ...ated ter minals parallel with the terminals the crimping screw torque is 2 0 0 1N m A click sound will be heard when the connector assembly is correct Use an open end wrench to tighten the waterproof...

Page 14: ...BAT CAN RS485 BAT NTC...

Page 15: ...Multi Inverter Parallel...

Page 16: ...otector or breaker first before connecting emove insulation sleeve 11mm 0 5 inch length unscrew the bolts insert the AC input wires according to polarities indicated on the terminal block and tighten...

Page 17: ...STEP 2 STEP 3 GRID EPS Load GRID EPS Load Fix the AC wiring cover with cover screws...

Page 18: ...nstall the CT Meter and a current sensor CT for short below are used to detect current power direction of the local load and the grid The output control function of the inverters will be activated bas...

Page 19: ...nication The monitoring module could transmit the data to the cloud server and display the data on the PC tablet and smart phone WIFI Ethernet GPRS RS485 communication is applicable to the inverter Pl...

Page 20: ...module flashes indicating that the monitoring module is successfully connected Note Note A second protective earth PE terminal should be connected to the inverter This prevents electric shock if the...

Page 21: ...y Fix the grounding screw to the grounding connection of the machine housing STEP 2 Operation Control Panel No Items No Items 1 LCD Display 5 UP Touch Button 2 POWER LED Indicator 6 DOWN Touch Button...

Page 22: ...e inverter is stand by OFF The inverter is power off GRID ON Green The inverter is feeding power OFF The inverter is not feeding power FAULT ON Red Fault occurred OFF No fault 3 6kW hybrid inverter ha...

Page 23: ...ter Any doubts please contact distributor for more details Inverter Setting System parameters setting System parameters setting Safety Specifications Note Select the safty according to the requirement...

Page 24: ...V Mode Operating parameters setting Operating parameters setting 1 No PV connection 2 Independent and Parallel setting for professional installers 5 4 3 2 5 4 3 2 Note Please select the right battery...

Page 25: ...fer to chapter 3 2 of the user manual Operating parameters setting Operating parameters setting Energy management system parameters setting 1 Self Use 2 Back Up 3 Selling First 4 Maintain In developme...

Page 26: ...arge discharge power range 10000W 10000W 1 Upper state of charge 2 Lower state of charge 3 Battery Overvoltage Threshold 4 Battery undervoltage threshold 5 Maximum charging current 6 Maximum discharge...

Page 27: ...e 1 6 AC charging can be set up to three time periods Energy management system parameters setting 5 4 3 2 Energy management system parameters setting Forced Charging Forced charging 5 4 3 2 1 ForceChg...

Page 28: ...und detection 4 Voltage upper limit 5 Voltage upper limit time 6 Voltage lower limit 7 Voltage lower limit time 8 Frequency upper limit 9 Frequency upper limit time 10 Frequency lower limit 11 Frequen...

Page 29: ...enEn Diesel generator enable 2 TimeCtr1Em Time control enable 3 TimeDelay Delay time of diesel generator start working 4 StarSoc Battery power percentage when diesel generator start charging the batte...

Page 30: ...hybrid inverter should be set following Chapter 5 3 at the first time When inverter running under normal mode Running indicator will light up Ref to Chapter 5 1 Restart Hybrid inverter please follow...

Page 31: ...cation If the fault occurs contin ously and frequently please ask help for local distribu tors A04 Pv1OverVoltFault PV Voltage over Reconfiguration of PV strings reduce the PV number of a PV string to...

Page 32: ...ault A41 Pv9AbnormalFault A42 Pv10AbnormalFault A43 Pv11AbnormalFault A44 Pv12AbnormalFault A45 Pv13AbnormalFault A46 Pv14AbnormalFault A47 Pv15AbnormalFault A48 Pv16AbnormalFault A49 Pv17AbnormalFaul...

Page 33: ...atTempSenso rOpen Battery temperature sensor abnormal Check battery temperature sensor and connected wires damage or not then rectifi cation or change new one B08 PcsBatTempSen sorShort B09 BmsBatSyst...

Page 34: ...will restart au tomatically when the grid return to normal Check inverter connected with grid connectors and ca ble normal or not C02 GridUnbalanVolt Fault Grid Voltage unbal anced The inverter will r...

Page 35: ...r will restart auto matically when the grid three phase return to normal Contact with local distribu tor or required grid company adjust frequency protection parameters C10 GridUnderFreqFault Grid Fre...

Page 36: ...urrent over triggered by Software logic Power off power on then restart If those faults occurs continuously and frequent ly please ask help for local distributors E14 Pv2SwOverCurrFault E15 Pv3SwOverC...

Page 37: ...BalBridge HwOverCurFault Bus Controller cur rent over Power off then restart Ref Chapter8 If those faults continuously and frequently please ask help for local distributors E52 BusBalBridg eSwOverCurF...

Page 38: ...r local distribu tors F09 PLLFault PLL abnormal Power off then restart Ref Chapter8 If those fault occurs contin uously and frequently please ask help for local distribu tors F10 GridRelayFault Grid r...

Page 39: ...If those faults occurs continuously and frequent ly please ask help for local distributors G02 PV2CurAdChanFault G03 PV3CurAdChanFault G04 PV4CurAdChanFault G05 PV5CurAdChanFault G06 PV6CurAdChanFaul...

Page 40: ...nt temperature over or low Change or improve the installation environment temperature make running temperature suitable Power off then restart Ref Chapter8 If those faults occurs continuously and freq...

Page 41: ...er CPU abnormal I10 HmiComWarning HMI abnormal I11 FreqCalcCon flictWarning Frequency value ab normal I12 UnsetModel Running model is not initial Contact with local distrib utor Outside Warnning J01 M...

Page 42: ...ef Chapter8 If this those faults continu ously and frequently please ask help for local distribu tors J05 ParallelComWarn ing Communication be tween master invert er and slaver ones abnormal in parall...

Page 43: ...40 60 Battery Type Li ion Lead acid etc AC GRID Max Continuous Current A 17 0 Max Continuous Power kVA 3 6 Nominal Grid Current A 16 4 15 7 Nominal Grid Voltage V 198 to 242 220 207 to 253 230 Nominal...

Page 44: ...tion Yes Enclosure Protect Level IP65 NEMA4X GENRAL DATA VT 6607136 Dimensions L x W x H mm 370 x 513 x 192 Weight kg 17 Topology Transformerless Cooling Intelligent Fan Relatively Humidity 0 100 Oper...

Page 45: ...gh London UK Postcode SL1 6BW Thank you for selecting and buying V TAC Product V TAC will serve you the best Please read these instructions carefully keep this user manual handy for future reference I...

Page 46: ...therwise agreed herein this manual will only be used as guidance Any statement information or suggestion in this manual will not take any form of responsibility Without written permission any content...

Page 47: ...ove the Module 1 WIFI MODULE INSTALLATION Implication Lights Status Description All lights are single green lights Communication with router Communication with inverter WIFI Module running status 1 Li...

Page 48: ...cess to the network 2 Check the router s setting if the connection is limited 3 Contact our customer service 1 Check the connection between WIFI Module and inverter Remove the WIFI Module and install...

Page 49: ...ethods and key press descriptions for Reset button NOTICES FOR RESET BUTTON USER MANUAL FOR SOLARMAN SMART APP Notice Do not remove waterproof plug Key press Status Descrip on Light Status Short press...

Page 50: ...packaging or on the logger body 4 Network Configuration After the logger is added please configure the network to ensure normal operation Go to Plant Details Device List find the target SN and click...

Page 51: ...heck plant data Usually the data will be updated in 10 mins If configuration failure occurs please check the following reason and try it again 1 Make sure WLAN is ON 2 Make sure WiFi is normal 3 Make...

Page 52: ...V DUUDQW DUG 0RQLWRULQJ 4XLFN Q DOODWLRQ Q UXFWLRQV DOO 0RXQWLQJ UDFNHW LULQJ RYHU 6FUHZ 6HFXULW 6FUHZ 1 1 1 1 1 2 3 3 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 CT LULQJ 7HUPLQDO AC WDW...

Page 53: ...UUHFW Note 3OHDVH XVH 39 FRQQHFWRU FULPSHU WR SLQFK WKH SRLQW RI WKH DUURZ 1 2 Note DWWHU FDEOH VXJJH LRQ URVV VHFWLRQ 19 1mm 3DVV WKH FULPSHG EDWWHU KDUQHVV WKURXJK WKH ZDWHUSURRI FRQQHFWRU DQG WKH F...

Page 54: ...2 3 RS485A 6 4 5 56 BAT 485 CAN 485 1 2 Note DEOH VXJJH LRQ URVV VHFWLRQ Note 7KH 0D SRZHU ORDG FRQQHFWV WR 36 SRUW VKRXOG QRW H FHHG WKH LQYHUWHU V 36 0D RXWSXW SRZHU UDQJH Note 7KH ZLULQJ WHUPLQDOV...

Page 55: ...version PRO version WIFI CONNECTION GROUND CONNECTION Con gure the Monitor Module router account registration etc Please check the WiFi connection manual for details 2 1 Note DUWK FDEOH 3 VXJJH LRQ U...

Reviews: