12-5
Modbus Communication
AC10 Inverter
Reading
parameter
address
Function
Remarks
100A
Read integer power value
The integer power value is read by PC.
100B
DI terminal status
DI1~DI8—bit0~bit7
100C
Terminal output status
bit0-OUT1 bit2-fault relay
100D
AI1
0~4095 read input analog digital value
100E
AI2
0~4095 read input analog digital value
1010
Reserved
1011
Reserved
1012
Reserved
1013
Present-stage speed value
0000 : no function
0001 : stage speed 1
0010 : stage speed 2
0011 : stage speed 3
0100 : stage speed 4
0101 : stage speed 5
0110 : stage speed 6
0111 : stage speed 7
1000 : stage speed 8
1001 : stage speed 9
1010 : stage speed 10
1011 : stage speed 11
1100 : stage speed 12
1101 : stage speed 13
1110 : stage speed 14
1111 : stage speed 15
Monitoring in which stage speed inverter is.
(Valid when F500 = 1 or F500 = 2)
1014
Reserved
1015
AO1
(
0~100.00
)
Monitoring analog output percent
1016
AO2
(
0~100.00
)
Monitoring analog output percent
1017
Current speed
Monitoring current speed.
1018
Read accurate power value Correct the power to 1 decimal place.
12.6.3 Control commands
Parameters
Address
Parameters Description
(
write only
)
2000
Command meaning:
0001
:
Forward running (no parameters
)
0002
:
Reverse running
(
no parameters
)
0003
:
Deceleration stop
0004
:
Free stop
0005
:
Forward jogging start
0006
:
Forward jogging stop
0007
:
Fault reset
000A: Forward jogging stop
Содержание 10G-46-0600-BF
Страница 2: ......
Страница 18: ...Installation 3 3 AC10 Inverter 3 3 Inverters Installed in a Control Cabinet...
Страница 26: ...Installation Connection 7 2 AC10 Inverter Metal Cover Layout Frames 6 11...
Страница 112: ...The Default Applications 13 2 AC10 Inverter 13 1Application 1 Basic Speed Control F228 1...
Страница 114: ...The Default Applications 13 4 AC10 Inverter 13 2 Application 2 Auto Manual Control F228 2...
Страница 116: ...The Default Applications 13 6 AC10 Inverter 13 3 Application 3 Preset Speeds F228 3...
Страница 118: ...The Default Applications 13 8 AC10 Inverter 13 4 Application 4 Raise Lower Secondary F228 4...
Страница 120: ...The Default Applications 13 10 AC10 Inverter 13 5Application 5 PID F228 5...