109
4-3
Fuzzy Constant Commands (Fuzzy-logic Controllers Only)
This section describes the commands that are used to read and write fuzzy
constants.
4-3-1 Fuzzy Constant Write Commands
This section covers the commands that are used to set fuzzy constants: the
fuzzy strength, fuzzy scale 1, and fuzzy scale 2.
Command Formats
Designate the point and memory bank to set the fuzzy constant. Fuzzy strength
cannot be set automatically. Autotuning PID constants automatically sets the
values of fuzzy scales 1 and 2. If the PID constants have been manually set, the
values of fuzzy scales 1 and 2 automatically changes according to the PID
constants. It is possible to change the values of fuzzy scales 1 and 2 manually
after the PID constants are set.
The header code varies with the fuzzy constant to be set. These commands can-
not be used while autotuning is being executed.
Fuzzy Strength Write: Wj
Designate a fuzzy strength value between 0000 and 0099 in increments of 1%. If
0000 is designate, the Temperature Controller will control the temperature using
only PID with feed-forward circuitry.
@
0
Unit
W
j
Bank Point
0
0
s
Fuzzy strength
*
FCS
Header code
(j in lower
case)
Data code
0000 to 0099
In increments of
1%
Terminator
Fuzzy Scale 1 Write: Wk
Designate a fuzzy scale 1 value between 0002 and 9999 in increments of 0.1
°
C
or 0.1
°
F.
*
@
0
Unit
W
k
Bank Point
0
0
s
FCS
Header code
(k in lower case)
Data code
Terminator
0002 to 9999
The position of the imaginary decimal
(in increments of 0.1
°
C/
°
F)
Fuzzy scale 1
Fuzzy Scale 2 Write: Wl
Designate a fuzzy scale 2 value between 0020 and 9999 in increments of
0.01
°
C/s or 0.01
°
F/s.
*
@
0
Unit
W
I
Bank Point
0
0
s
FCS
Header code
(I in lower case)
Data code
Terminator
0020 to 9999
The position of the imaginary decimal
(in increments of 0.01
°
C/s or 0.01
°
F/s)
Fuzzy scale 2
Command Example
The following command is used to set the Temperature Controller to a fuzzy
strength of 25% in memory bank 3 of point 2 in unit 1.
*
@
0
1
W
j
3
2
0
0
0
0
2
5
7
A
s
25%
Fuzzy Constant Commands (Fuzzy-logic Controllers Only)
Section 4-3
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...