32
and the Pt100 setting will be -100.0
°
C to 200.0
°
C for platinum resistance ther-
mometer specifications. The Celsius/Fahrenheit setting is made on SW503.
Pin
0
1
2
3
Sensor type
K
J
°
C
0
°
to 400
°
C
0
°
to 600
°
C
0
°
to 400
°
C
0
°
to 600
°
C
°
F
32
°
to 752
°
F
32
°
to 1112
°
F
32
°
to 752
°
F
32
°
to 1112
°
F
Pin
0
1
2
3
Sensor type
Pt100
JPt100
°
C
–100.0
°
to
200.0
°
C
0
°
to 500
°
C
–100.0
°
to
200.0
°
C
0
°
to 500
°
C
°
F
–148.0
°
to
392.0
°
F
32
°
to 932
°
F
–148.0
°
to
392.0
°
F
32
°
to 932
°
F
Function Switch: SW503
SW503 determines some of the basic operating parameters of the E5ZD, as
shown in the following table. These settings are described below. Switch ap-
pearance and pin number are the same as SW502, shown above. All pins are
set to OFF at the factory.
SW503
ON
OFF
Pin
Function
ON
OFF
1
Operation mode
Test
Normal
2
Memory bank designation
Inputs
Communications
3
Unit of measure
Fahrenheit
Celsius
4
Initial status
Operating
Non-operating
Pin 1
Pin 1 determines whether the normal operation mode or the communications
test mode (the mode in which the loop-back test is executed) is to be used. If pin
1 is set to ON and then power is applied to the E5ZD, the communications test
mode will be used and the following character string will be sent continuously
until the power is cut. Reception should be confirmed at the host computer. A
loop-back test will be conducted simultaneously to see whether the E5ZD can
receive the transmitted data back again. If it cannot receive the data back just as
it was transmitted, a Temperature Controller alarm output will turn ON.
E5ZD
Ć
Copyright
Ć
1991
Ć
OMRON
Ć
Corporation
s
(carriage return)
Pin 2
Pin 2 determines whether the current memory bank is to be set according to in-
put status or via communications from the host computer. If pin 2 is set to ON
before power is turned ON, the status of the BANK0, BANK1, BANK2, and ING
terminals will determine the current memory bank. If pin 2 is OFF, the current
memory bank will be determined according to commands sent from the host
computer.
Pin 3
Pin 3 determines whether Fahrenheit or Celsius is to be used. (Fahrenheit and
Celsius can be manually converted via this equation:
°
F = 1.8
×
°
C + 32.)
Pin 4
Pin 4 determines E5ZD operation in response to power interruptions during con-
E5ZD-8
jj
KJ-E
E5ZD-8
jj
P-E
E5ZD-8
jjj
-E Hardware
Section 2-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...