110
Take the decimal position into consideration when writing the fuzzy scale 1 value
(increments of 0.1), and when writing the fuzzy scale 2 value (increments of
0.01).
Response Format
The response returned for this command is shown below. This response as-
sumes that the header code in the command block was transmitted and read
normally. If the header code in the command block was not recognizable, a
header code of IC will be returned without an end code (see
Section 4-1-2 End
Codes
for the IC header code response format).
@
0
Unit W
j/k/l
CR
Header code
Terminator
*
End code
FCS
End Codes
If an end code of 00 was returned in the response, the command was executed
normally. If the end code is not 00, the desired data will not have been written.
Refer to
Section 4-1-2 End Codes
for a description of the other possible end
codes and their meanings.
4-3-2 Fuzzy Constant Read Commands
This section covers the commands that are used to read fuzzy constants: fuzzy
strength, fuzzy scale 1, and fuzzy scale 2. The value of fuzzy scale 1 is returned
to the nearest 0.1
°
C. The value of fuzzy scale 2 is returned to the nearest 0.01
°
C.
Designate the point and memory bank to read the fuzzy constant. The header
code varies with the fuzzy constant to be read.
Command Formats
Fuzzy Strength Read: Rj
Fuzzy strength is returned between 0000 and 0099 with increments of 1%.
@
0
Unit
R
j
Bank Point
0
0
s
*
FCS
Header code
(j in lower case)
Data code
Terminator
Fuzzy Scale 1 Read: Rk
Fuzzy scale 1 is returned between 0002 and 9999 in increments of 0.1
°
C or
0.1
°
F.
*
@
0
Unit
R
k
Bank Point
0
0
s
FCS
Header code
(k in lower case)
Data code
Terminator
Fuzzy Scale 2 Read: Rl
Fuzzy scale 2 is returned between 0020 to 9999 in increments of 0.01
°
C/s or
0.01
°
F/s.
*
@
0
Unit
R
I
Bank Point
0
0
s
FCS
Header code
(i in lower case)
Data code
Terminator
Fuzzy Constant Commands (Fuzzy-logic Controllers Only)
Section 4-3
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...