20
RS-422 Interface
Pin assignments and specifications for RS-422 communications are provided
below.
•
Electrical characteristics: Conform to EIA RS-422
•
Signal connections: As shown below
Signal name
Symbol
Direction
Pin
Send data A
SDA
Output
9
Send data B
SDB
Output
5
Receive data A
RDA
Input
6
Receive data B
RDB
Input
1
Signal ground
SG
NA
3
•
Connection diagram:
You can use RS-422 to connect up to 16 controllers to one host.
Symbol
FG
Symbol
Pin. no
9
5
6
6.8 V
RDA
RDB
SDA
SDB
SG
SDA
SDB
RDA
RDB
SG
1
3
Symbol
Pin. no
9
5
6
SDA
SDB
RDA
RDB
SG
1
3
Shielded
cable
Shielded cable
Host computer
RS-422
E5ZD
RS-422
MC34050 or
equivalent
4.7 k
Ω
4.7 k
Ω
TX
RX
Termination resistance
220
Ω
SWB
SWA
220
Ω
Termination
resistance
E5ZD
RS-422
Termination
resistance
Termination resis-
tance (220
Ω
)
can be set via SWA
and SWB.
Termination resistance
(terminator, must be 100
Ω
or
greater)
•
Sync clock:
Internal
•
Transmission length:
500 m total max.
•
Terminator switches:
E5ZD-4/-6
j
02
j
-E: SWB corresponds to SW8.
E5ZD-8
j
02
j
-E:
SWB corresponds to SW508.
E5ZD-8H02
j
M-E: SWB corresponds to SW508.
•
Applicable connectors: Plug, XM2A-0901; hood, XM2S-0911 (OMRON)
or equivalent
•
Connections:
Up to 1:16
Caution
Output circuits and contact input circuits are not electrically insulated from the
transmission circuits in 4- and 6-point controllers.
E5ZD-4
jjj
-E
/
-6
jjj
-E
Hardware
Section 2-1
5
1
6
9
RS-422 Pin Assignments
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...