77
Integral Time Write: WN
The integral time is input in seconds (between 0000 and 3999). Setting 0000 will
turn integral operation OFF.
Header code
@
0
Unit W
N
Bank Point
0
0
CR
0000 to 3999, Unit: 1 s
Data code
*
Terminator
Integral time
FCS
Derivative Time Write: WV
The derivative time is input in seconds and can be between 0000 and 3999. Set-
ting 0000 will turn derivative operation OFF.
@
0
Unit W
V
Bank Point
0
0
CR
Header code
0000 to 3999, Unit: 1 s
Data code
*
Terminator
Derivative time
FCS
Control Period Write: WT
The control period is input in seconds and can take a value between 0001 and
0099.
@
0
Unit W
T
Bank Point
0
0
CR
Header code
0001 to 0099, Unit: 1 s
Data code
*
Terminator
Control period
FCS
Command Examples
The following command is used to set a 50
°
C proportional band in memory bank
3 for control point 2 of unit 1.
@ 0
1
W
B
3
2
0
0
0
5
0
0
5
0
CR
50. 0
°
C
*
Response Formats
The responses returned for these commands are shown below. These re-
sponses assume that the header code in the command block was transmitted
and read normally. If the header code in the command block was not recogniz-
able, a header code of IC will be returned without an end code (see
Section 4-1-2
End Codes
for the IC header code response format).
@
0
Unit W
CR
Header code
FCS
*
Terminator
End code
B: For proportional band
N: For integral time
V: For derivative time
T: For control period
Temperature Control Commands (All Controllers)
Section 4-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...