28
ity is detected within the E5ZD. CT terminals are not polarity sensitive and may
be connected as desired to the CT input terminals.
Terminal
Row a (bottom)
Row c (top)
Name
Function
Name
Function
1
ALARM1G
Alarm output 1 (–)
ALARM1
Alarm output 1 (+)
2
ALARM2G
Alarm output 2 (–)
ALARM2
Alarm output 2 (+)
3 to 14
Not used.
Not used.
15
HBALMG
HB alarm output (–)
HBALM
HB alarm output (+)
16
HSALMG
HS alarm output (–)
HSALM
HS alarm output (+)
17
Not used.
Not used.
18
TCTRBLG
Error output (–)
TCTRBL
Error output (+)
19 to 24
Not used.
Not used.
25
CT0
Point 0 CT input
CT0
Point 0 CT input
26
CT1
Point 1 CT input
CT1
Point 1 CT input
27
CT2
Point 2 CT input
CT2
Point 2 CT input
28
CT3
Point 3 CT input
CT3
Point 3 CT input
29
CT4
Point 4 CT input
CT4
Point 4 CT input
30
CT5
Point 5 CT input
CT5
Point 5 CT input
31
CT6
Point 6 CT input
CT6
Point 6 CT input
32
CT7
Point 7 CT input
CT7
Point 7 CT input
Power Supply Terminals
Power is supplied to the 8-point controllers through the DC+ and DC– terminals.
Connect the DC+ terminals to 24 VDC; the DC– terminals to 0 VDC. The rated
voltage (21.6 to 26.4 VDC) must be supplied to the DIN connector on the E5ZD;
these are not switching power-supply terminals.
To ensure activation of the power supply, it is necessary that at least twice the
rated current capacity be available when power is turned on.
Memory Bank Terminals
The BANK0, BANK1, BANK2, and three ING terminals can be used to select the
memory bank to be used for temperature control. Refer to
Section 3-3 Memory
Banks
for operational details. The BANK0, BANK1, and BANK2 terminals are
activated by connecting each to a ING terminal. The terminals can be connected
either through contacts, e.g., relays, or through transistors or other no-contact
devices. The memory banks designated by the various open-closed combina-
tions of these terminals are shown in the following table.
Memory bank
Bank 0
Bank 1
Bank 2
Bank 3
Bank 4
Bank 5
Bank 6
Bank 7
BANK0-ING
Open
Closed
Open
Closed
Open
Closed
Open
Closed
BANK1-ING
Open
Open
Closed
Closed
Open
Open
Closed
Closed
BANK2-ING
Open
Open
Open
Open
Closed
Closed
Closed
Closed
E5ZD-8
jjj
-E Hardware
Section 2-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...