100
Initialize Parameters does not affect the contents of EEPROM. To save the de-
fault values (or further modifications of them) to EEPROM, use EEPROM Write.
Initialize Parameters can be used only when the E5ZD is stopped and only for all
control points at once, i.e., control points cannot be individually initialized.
The values inside of the parentheses are the default setting when the setting unit
is 0.1.
Parameter
Default
Remarks
HB/HS alarm point
0000
All control points OFF
Current memory bank
0000
Bank 0 for all control points
Output mode
0000
Heating operation for all control points
Alarm 1 mode
0000
No alarm for all control points
Alarm 2 mode
0000
No alarm for all control points
HB alarm level
0000
No HB alarm for all control points
Set temperature
°
C:
0000 (00000)
0
°
C
°
F:
0032 (00320)
32
°
F
Hysteresis
°
C: 0008
0.8
°
C
°
F:
0015
1.5
°
F
Input shift
0000
No shift
Proportional band
0000
ON/OFF operation
Integral time
0000
No integral operation
derivative time
0000
No derivative operation
Control period (heating side)
0002
2 seconds
Alarm 1 alarm temperature
0000 (00000)
0
°
C/0
°
F
Alarm 2 alarm temperature
0000 (00000)
0
°
C/0
°
F
Fuzzy strength
0050
50% of full strength
Fuzzy scale 1
9999
999.9
°
C or 999.9
°
F
Fuzzy scale 2
9999
99.99
°
C/s or 99.99
°
F/s
Command Format
The format for this command is as shown below. The unit number must be speci-
fied.
@
0
Unit M
C
CR
Header code
Terminator
*
FCS
Command Examples
The following command is used to initialize parameters for Unit 1.
@ 0
1
M
C
4
F
CR
*
Response Format
The response returned for this command is shown below. This response
assumes that the header code in the command block was transmitted and read
normally. If the header code in the command block was not recognizable, a
Temperature Control Commands (All Controllers)
Section 4-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...