96
Command Format
The format for this command is as shown below. The unit number, memory bank,
and control point must be specified.
@
0
Unit
R
I
Bank Point
0
0
CR
Header code
(Alphabet)
Terminator
*
Data code
FCS
Response Format
The response returned for this command is shown below. This response as-
sumes that the header code in the command block was transmitted and read
normally and that the end code is 00. If the end code is not 00, the shift value will
not have been read and the end code will be followed immediately by a frame
check sequence (FCS). If the header code in the command block was not recog-
nizable, a header code of IC will be returned without an end code (see
Section
4-1-2 End Codes
for the IC header code response format).
@
0
Unit R
I
End
code
CR
Header
code
(Alphabet)
Terminator
*
Sign
x10
1
x10
0
x10
–1
(0,-)
Imaginary decimal point
Input shift
FCS
Response Examples
This response shows that a shift value of 12.3
°
C has been set in memory bank 0
of point 0 in unit 2.
@ 0
2
R
I
2
1
0
0
0
1
2
3
4
2
CR
*
12. 3
°
C
End Codes
If an end code of 00 was returned in the response, the command was executed
normally. If the end code is not 00, the desired data will not have been be read.
Refer to
Section 4-1-2 End Codes
for a description of the other possible end
codes and their meanings.
4-2-20 Hysteresis
Write:
WH
This command is used to set the hysteresis used in ON/OFF operation. Doing so
will result in an error and the end code 01 will be returned.
Note
It cannot be used during autotuning.
Command Format
The format for this command is as shown below. The unit number, memory bank
number, and control point must be specified along with the hysteresis. The hys-
teresis is given in three digits to an accuracy of one-tenth of a degree.
@
0
Unit W
H
Bank Point
0
0
0
CR
x10
1
x10
0
x10
–1
Hysteresis
FCS
Header code
Terminator
*
Imaginary decimal point
Data code
Always
0
Temperature Control Commands (All Controllers)
Section 4-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...