16
CN2
Terminal Assignments
The following table shows the terminal assignments for CN2. All alarm and error
outputs are open-collector outputs.
Note
Open-collector outputs are not protected from excessive current flow; be sure to
wire them correctly to protect internal circuits from damage.
ALARM1G and ALARM2G are the emitters and ALARM1 and ALARM2 are the
collectors for alarm 1 and alarm 2, respectively. The HB alarm output goes ON
when the detected current falls below the set heater current. The HS alarm out-
put goes ON when there is a current flow of 0.5 A or more on the CT when the
control output of the E5ZD is OFF. The error output goes ON when an abnormal-
ity is detected within the E5ZD. CT terminals are not polarity sensitive and may
be connected as desired to the CT input terminals. The same signals as on CN6
are placed on terminals 22 through 24 when RS-422 or RS-485 communications
are used. For the E5ZD-4
jjj
-E, terminals 31 and 32 are also not used.
Terminal
Row a (bottom)
Row b (top)
Name
Function
Name
Function
1
ALARM1G
Alarm output 1 (–)
ALARM1
Alarm output 1 (+)
2
ALARM2G
Alarm output 2 (–)
ALARM2
Alarm output 2 (+)
3 to 14
Not used.
Not used.
15
HBALMG
HB alarm output (–)
HBALM
HB alarm output (+)
16
HSALMG
HS alarm output (–)
HSALM
HS alarm output (+)
17
Not used.
Not used.
18
TCTRBLG
Error output (–)
TCTRBL
Error output (+)
19 to 21
Not used.
Not used.
22
SG
RS-422: SG
Not used.
23
SDA, (–)
RS-422: SDA, RS-485: (–)
SDB, (+)
RS-422: SDB, RS-485: (+)
24
RDA
RS-422: RDA
RDB
RS-422: RDB
25 and 26
Not used.
Not used.
27
CT0
Point 0 CT input
CT0
Point 0 CT input
28
CT1
Point 1 CT input
CT1
Point 1 CT input
29
CT2
Point 2 CT input
CT2
Point 2 CT input
30
CT3
Point 3 CT input
CT3
Point 3 CT input
31
CT4
Point 4 CT input
CT4
Point 4 CT input
32
CT5
Point 5 CT input
CT5
Point 5 CT input
CT Inputs
CT terminals are not polarity sensitive and may be connected as desired to the
CT input terminals.
CT input
E54-CT1/CT3
CT input
E5ZD
Sensor Connections
Temperature sensor lead wires are connected to TB1 as shown below. Be sure
to secure the lead wires so that they do not come into contact with E5ZD compo-
nents.
E5ZD-4
jjj
-E
/
-6
jjj
-E
Hardware
Section 2-1
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...