34
Meanings
No.
Function
Indicator lit.
Indicator not lit.
1
Reset Monitor
CPU resetting. (Note 1)
CPU operating.
2
Operation monitor 1
Monitors 1 and 2 both lit: Memory error.
Monitor 1 not lit, monitor 2 lit: Communications error. (Note 2)
3
Operation monitor 2
(
)
Monitor 1 lit, monitor 2 not lit: Point exists during AT. (Note 3)
Monitors 1 and 2 both not lit: None of the above.
4
Memory bank 0
Memory bank setting 2
0
input.
Memory bank setting 2
0
open.
5
Memory bank 1
Memory bank setting 2
1
input.
Memory bank setting 2
1
open.
6
Memory bank 2
Memory bank setting 2
2
input.
Memory bank setting 2
2
open.
7
Not used
8
Reception monitor
E5ZD receiving.
E5ZD not receiving.
9
Transmission monitor
E5ZD transmitting.
E5ZD not transmitting.
10
Temperature Controller alarm output
Output ON
Output OFF
11
HS alarm output
Output ON
Output OFF
12
HB alarm output
Output ON
Output OFF
13
Alarm 2 output
Output ON
Output OFF
14
Alarm 1 output
Output ON
Output OFF
15
Point 0 control output
Output ON
Output OFF
16
Point 1 control output
Output ON
Output OFF
17
Point 2 control output
Output ON
Output OFF
18
Point 3 control output
Output ON
Output OFF
19
Point 4 control output
Output ON
Output OFF
20
Point 5 control output
Output ON
Output OFF
21
Point 6 control output
Output ON
Output OFF
22
Point 7 control output
Output ON
Output OFF
23
Power supply monitor
Power supply ON
Power supply OFF
Note
1. During E5ZD-8
jjj
-E CPU resetting, the E5ZD will not operate and cannot
communicate. The reset indicator will light for approximately 1 second after
the power is applied or after a malfunction due to a cause such as noise.
2. This type of error would be a framing error, a parity error, or an overrun error.
3. AT: Autotuning
2-3
E5ZD-8H
jj
M-E Hardware
2-3-1
E5ZD-8H
j
KJM-E System Configuration
The E5ZD-8H
j
KJM-E has connectors for thermocouple input and output, so
the Terminal Block can be connected by a cable and positioned in a remote loca-
tion. When a Terminal Block or an I/O Relay Terminal is connected to any of the
connectors (CN324 to CN327), GT9-
jjj
C cable must be used. Placing the
cable in the vicinity of machines which emit noise or where there are electrical
surges can cause malfunctioning, so separate them as much as possible from
such areas and ground both ends with shielding.
CN324 and CN325 connect Terminal Blocks for thermocouple inputs.
E54-TR011 Terminal Blocks can be used. If these special Terminal Blocks are
not used, a cold contact error will be generated and the temperature cannot be
controlled.
CN324 is for sensor input from points 0 to 3, and CN325 is for sensor input from
points 4 to 7.
CN326 connects through-type Terminal Blocks. XW2B-20G4 or XW2B-20G5
Terminal Blocks can be used. When E54-CT1 or E54-CT3 Current Transformers
Thermocouple Inputs
(CN324, CN325)
Memory Bank Designation
and CT Inputs (CN326)
E5ZD-8H
jj
M-E Hardware
Section 2-3
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...