86
Response Format
The response returned for this command is shown below. This response as-
sumes that the header code in the command block was transmitted and read
normally. If the header code in the command block was not recognizable, a
header code of IC will be returned without an end code (see
Section 4-1-2 End
Codes
for the IC header code response format).
@
0
Unit W
M
CR
Header code
Terminator
*
FCS
End code
End Codes
If an end code of 00 was returned in the response, the command was executed
normally. If the end code is not 00, the desired data will not have been written.
For WM, a 01 end code will be generated if the memory bank designation meth-
od has been set to “contact valid” by the DIP switch (it is set to “communications
valid” at the time of shipping.). Refer to
Section 4-1-2 End Codes
for a descrip-
tion of the other possible end codes and their meanings.
4-2-11
Memory Bank Designation Read: RM
This command is used to read out which memory bank is currently specified for a
specified control point.
Command Format
The format for this command is as shown below. The unit number and control
point must be specified.
@
0
Unit R
M
0
Point
0
0
CR
Header code
Terminator
*
Data code
FCS
Always 0.
Response Format
The response returned for this command is shown below. This response as-
sumes that the header code in the command block was transmitted and read
normally and that the end code is 00. If the end code is not 00, the desired data
will not have been read and the end code will be followed immediately by the
FCS. If the header code in the command block was not recognizable, a header
code of IC will be returned without an end code (see
Section 4-1-2 End Codes
for
the IC header code response format).
@
0
Unit R
M
0
0
0
Bank
CR
Selectable memory banks: 0 to 7
Terminator
*
End code
FCS
Header code
Response Examples
This response shows that memory bank 3 is currently specified for control point
0 of unit 2.
*
@ 0
2
R
M
0
0
0
0
0
3
5
E
CR
Temperature Control Commands (All Controllers)
Section 4-2
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...