Parameter Defaults, Setting Ranges and Instructions
Appendix B
134
Commands for Parameters Contained in Memory Banks
Parameter
Write code
Read
code
Digits
Default
Upper
Lower
Remarks
Set Temperature
WS
RS
4
0000
FS
FS
Unit: 1
°
C
0032
FS
FS
Unit: 1
°
F
5
00000
FS
FS
Unit: 0.1
°
C
00320
FS
FS
Unit: 0.1
°
F
Proportional Band
WB
RB
4
0000
0000
9999
Unit: 1
°
C/
°
F
Integral Time
WN
RN
4
0000
0000
3999
Unit: s
Derivative Time
WV
RV
4
0000
0000
3999
Unit: s
Control Period
WH
RH
4
0002
0001
0099
Unit: s
Hysteresis
WH
RH
4
0008
0000
0999
Unit: 1
°
C
0015
0000
0999
Unit: 1
°
F
Input Shift
WI
RI
0000
–000
0999
Unit: 0.1
°
C/
°
F
Alarm Temperature
W%
R%
4
0000
–999
1999
Unit: 1
°
C/
°
F
5
00000
–9999
19999
Unit: 0.1
°
C/
°
F
Fuzzy Strength (Fuzzy-
logic Controllers only)
Wj
Rj
4
0050
0000
0099
Unit: 1%
Fuzzy Scale 1 (Fuzzy-
logic Controllers only)
Wk
Rk
4
9999
0002
9999
Unit: 0.1
°
C/
°
F
Fuzzy Scale 2 (Fuzzy-
logic Controllers only)
Wl (lower-
case l)
Rl (lower-
case l)
4
9999
0020
9999
Unit: 0.01
°
C/
°
F
Other Read Commands
Command
Header code
Digits
Remarks
Measured Temperature
Read
RX-00
4
Unit: 1
°
C
Read
5
Unit: 0.1
°
C
Heater Current Read
RZ
4
Unit: 0.1 A
Output Variable Read
RX-01
4
Unit: 0.1%
Output Variable Read
RO
4
Unit: 0.1%
Status Read
RX-02
4
Operating status of E5ZD
Error Read
RU-03
4
Specifies E5ZD error
Содержание E5ZD
Страница 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Страница 2: ......
Страница 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 8: ......
Страница 10: ......
Страница 18: ......
Страница 76: ......
Страница 128: ......
Страница 132: ......
Страница 142: ......
Страница 146: ......
Страница 148: ......
Страница 150: ......
Страница 154: ......
Страница 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...