Chapter 10
10-71
Appendices
00
66
0066
RS-422A/
485 commu-
nications
error
Monitors U1-39
Bit 0
CRC error
Bit 1
Invalid data length
Bit 2
Not used.
Bit 3
Parity error
Bit 4
Overrun error
Bit 5
Framing error
Bit 6
Time-out
Bits 7 to
F
Not used.
00
68
0068
Fan operat-
ing time
Monitors U1-40; 1-hr units
00
80
0080
Current fault
Monitors U2-01
Code
Error
display
Code
Error
display
Code
Error
display
01
PUF
0E
---
1C
---
02
UV1
0F
---
1D
OH3
03
UV2
10
---
1E
OPR
04
UV3
11
EF3
1F
ERR
06
GF
12
EF4
20
OH4
07
OC
13
EF5
22
BUS
08
OV
14
EF6
25
CF
09
OH
15
EF7
27
EF0
0A
OH1
18
---
28
FBL
0B
OL1
19
---
29
IL3
0C
OL2
1A
---
2A
---
0D
OL3
1B
---
2B
OL7
00
81
0081
Last fault
Monitors U2-02 (same codes as U2-01)
00
82
0082
Fault fre-
quency refer-
ence
Monitors U2-03; 0.01-Hz units (units set in o1-03; with sign)
00
83
0083
Fault output
reference
Monitors U2-04; 0.01-Hz units (units set in o1-03; with sign)
00
84
0084
Fault output
current
Monitors U2-05; Inverters of 7.5 kW or less: 0.01-A units,
Inverters of 11 kW or more: 0.1-A units
---
---
0085
Not used.
00
86
0086
Fault output
voltage refer-
ence
Monitors U2-07; 0.1-V units
00
87
0087
Fault main
circuit DC
voltage
Monitors U2-08; 1-V units
00
88
0088
Fault output
power
Monitors U2-09; 0.1-kW units (with sign)
---
---
0089
Not used.
Class 64
Register No.
(Hex)
Contents
In-
stance
At-
tribute
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...