Chapter 10
10-80
Appendices
Note 1.
The values in parentheses indicate initial values when initialized in 3-wire sequence.
Note 2.
Set H5-01 to 0 to disable Inverter responses to RS-422A/485 communications.
■
Protective Function Parameters
H4-01
041D
04
1D
Monitor selection (terminal
FM)
1 to 40
1
2
No
H4-02
041E
04
1E
Gain (terminal FM)
0.0 to
1,000.0
0.1%
100.0
Yes
H4-03
041F
04
1F
Bias (terminal FM)
−
110.0
to 110.0
0.1%
0.0
Yes
H4-04
0420
04
20
Monitor selection (terminal
AM)
1 to 40
1
3
No
H4-05
0421
04
21
Gain (terminal AM)
0.0 to
1,000.0
0.1%
50.0
Yes
H4-06
0422
04
22
Bias (terminal AM)
−
110.0
to 110.0
0.1%
0.0
Yes
H4-07
0423
04
23
Analog output 1 signal level
selection
0 or 2
1
0
No
H4-08
0424
04
24
Analog output 2 signal level
selection
0 or 2
1
0
No
H5-01
0425
04
25
Slave address
0 to 20
(See
note 2.)
1
1F
No
H5-02
0426
04
26
Communication speed
selection
0 to 4
1
3
No
H5-03
0427
04
27
Communication parity
selection
0 to 2
1
0
No
H5-04
0428
04
28
Stopping method after com-
munication error
0 to 3
1
3
No
H5-05
0429
04
29
Communication error detec-
tion selection
0 or 1
1
1
No
H5-06
042A
04
2A
Send wait time
5 to 65
1 ms
5
No
H5-07
042B
04
2B
RTS control ON/OFF
0 or 1
1
1
No
Param-
eter
Register
No.
(Hex)
Class 64 (Hex)
Name
Setting
range
Setting
unit
Default
setting
Changes
during
opera-
tion
In-
stance
At-
tribute
L1-01
0480
04
80
Motor protection selection
0 or 1
1
1
No
L1-02
0481
04
81
Motor protection time con-
stant
0.1 to
5.0
0.1 min
1.0
No
L1-03
0482
04
82
Alarm operation selection
during motor overheating
0 to 3
1
3
No
L1-04
0483
04
83
Motor overheating opera-
tion selection
0 to 2
1
1
No
L1-05
0484
04
84
Motor temperature input fil-
ter time constant
0.00 to
10.00
0.01 s
0.20
No
Param-
eter
Register
No.
(Hex)
Class 64 (Hex)
Name
Setting
range
Setting
unit
Default
setting
Changes
during
opera-
tion
In-
stance
At-
tribute
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...