Chapter 10
10-63
Appendices
Note 1.
Values in parentheses are for 400-V-class Inverters.
Note 2.
If the setting is 0, the axis will accelerate to the specified speed over the specified acceler-
ation time (C1-01 to C1-08).
Note 3.
The initial value when C6-01 is set to 1 is given. If C6-01 is set to 0, the initial value will be
150%.
Note 4.
Values in parentheses are for Asian model Inverters.
■
Special Adjustment Parameters
■
Operator Parameters
L8-10
04B6
04
B6
Cooling fan control selection
0, 1
1
0
No
L8-11
04B7
04
B7
Cooling fan control delay time
0 to 300
1 s
60
No
L8-12
04B8
04
B8
Ambient temperature
45 to 60
1
°
C
45
No
L8-15
04BB
04
BB
OL2 characteristics selection at low
speeds
0, 1
1
1
No
L8-18
04BE
04
BE
Soft CLA selection
0, 1
1
1
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
N1-01
0580
05
80
Hunting-prevention function selection
0, 1
1
1
No
N1-02
0581
05
81
Hunting-prevention gain
0.00 to
2.50
0.01
1.00
No
N2-01
0584
05
84
Speed feedback detection control
(AFR) gain
0.00 to
10.00
0.01
1.00
No
N2-02
0585
05
85
Speed feedback detection control
(AFR) time constant
0 to 2000 1 ms
50
No
N2-03
0586
05
86
Speed feedback detection control
(AFR) time constant 2
0 to 2000 1 ms
750
No
N3-01
0588
05
88
High-slip braking deceleration fre-
quency width
1 to 20
1%
5
No
N3-02
0589
05
89
High-slip braking current limit
100 to
200
1%
150
No
N3-03
058A
05
8A
High-slip braking stop dwell time
0.1 to
10.0
0.1 s
1.0
No
N3-04
058B
05
8B
High-slip braking OL time
30 to
1200
1 s
40
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
o1-01
0500
05
00
Monitor selection
4 to 33
1
6
Yes
o1-02
0501
05
01
Monitor selection after power up
1 to 4
1
1
Yes
o1-03
0502
05
02
Frequency units of reference setting
and monitor
0 to
39999
1
0
No
o1-05
0504
05
04
LCD brightness
0 to 5
1
3
Yes
o2-01
0505
05
05
LOCAL/REMOTE key enable/disable
0, 1
1
1
No
o2-02
0506
05
06
STOP key during control circuit termi-
nal operation
0, 1
1
1
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...