Chapter 10
10-37
Appendices
■
Function Group 2 (n050 to n079)
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n050
0132
01
32
Multi-function input 1 (terminal S1)
1 to 27
1
1
No
n051
0133
01
33
Multi-function input 2 (terminal S2)
1 to 27
1
2
No
n052
0134
01
34
Multi-function input 3 (terminal S3)
0 to 27
1
3
No
n053
0135
01
35
Multi-function input 4 (terminal S4)
1 to 27
1
5
No
n054
0136
01
36
Multi-function input 5 (terminal S5)
1 to 27
1
6
No
n055
0137
01
37
Multi-function input 6 (terminal S6)
1 to 27
1
7
No
n056
0138
01
38
Multi-function input 7 (terminal S7)
1 to 27,
34, 35
1
10
No
n057
0139
01
39
Multi-function input 1 (MA/MB-MC)
0 to 21
1
0
No
n058
013A
01
3A
Multi-function input 2 (P1-PC)
0 to 21
1
1
No
n059
013B
01
3B
Multi-function input 3 (P2-PC)
0 to 21
1
2
No
n060
013C
01
3C
Frequency reference gain
0 to 255
1%
100
Yes
n061
013D
01
3D
Frequency reference bias
−
100 to
100
1%
0
Yes
n062
013E
01
3E
Analog frequency reference filter time
constant
0.00 to
2.00
0.01 s
0.10
Yes
n063
---
---
---
Not used.
---
---
---
---
n064
0140
01
40
Frequency reference loss detection
selection
0, 1
1
0
No
n065
0141
01
41
Multi-function analog output type selec-
tion
0, 1
1
0
No
n066
0142
01
42
Multi-function analog output
0 to 6
1
0
No
n067
0143
01
43
Multi-function analog output gain
0.00 to
2.00
0.01
1.00
Yes
n068
0144
01
44
Multi-function analog voltage input gain
−
255 to
255
1%
100
Yes
n069
0145
01
45
Multi-function analog voltage input bias
−
100 to
100
1%
0
Yes
n070
0146
01
46
Multi-function analog voltage input filter
constant
0.00 to
2.00
0.01 s
0.10
Yes
n071
0147
01
47
Multi-function analog current input gain
−
255 to
255
1%
100
Yes
n072
0148
01
48
Multi-function analog current input bias
−
100 to
100
1%
0
Yes
n073
0149
01
49
Multi-function analog current input fil-
ter constant
0.00 to
2.00
0.01 s
0.10
Yes
n074
014A
01
4A
Pulse train frequency reference gain
−
255 to
255
1%
100
Yes
n075
014B
01
4B
Pulse train frequency reference bias
−
100 to
100
1%
0
Yes
n076
014C
01
4C
Pulse train frequency reference input
filter constant
0.00 to
2.00
0.01 s
0.10
Yes
n077
014D
01
4D
Multi-function analog input terminal
function selection
0 to 4
1
0
No
n078
014E
01
4E
Multi-function analog input terminal
selection
0, 1
1
0
No
n079
014F
01
4F
Multi-function analog input frequency
bias
0 to 50
1%
10
No
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...