Chapter 5
5-6
Remote I/O Functions
5-2-2 Switching with the Connection Path (Master)
Use the following procedure to switch the Master’s remote I/O function with the Configurator. In this
example, the remote I/O function is set to
Control I/O remote I/O + Unit status
.
■
Procedure
1.Locate the Master in the Network Configuration Window and either double-click the Master or
right-click and select
Parameters/Edit
from the pop-up menu to display the
Edit Device Parame-
ters
Window. Select the desired Slave from the
General
Tab Page.
2.Click the
Button to move the desired Inverter to the
Register Devices List.
Note
The
Register/Unregister
Button can be clicked at this point to allocate data with the remote
I/O function selected in the Slave. The following steps explain how to allocate data freely, so
steps 3 to 10 are not required if data will be allocated automatically. Proceed to step 11 (Down-
load) if using automatic allocation.
3.Select the desired Inverter from the
General
Tab Page and click the
Advanced Setup
Button.
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...