Configurator Settings
■
Setting Method
Click the
Warning Torque
Tab in the Edit Device Parameters Window, and set each setting item.
Note 1.
When
Current 1
is set to 0.0 (A), the warning torque during acceleration/deceleration is not
detected.
Note 2.
When
Current 2
is set to 0.0 (A), the warning torque during frequency agreement is not de-
tected.
Note 3.
A detection sensitivity level of 5 disables the filter. A detection sensitivity level of 1 uses the
average of 5 sampled current levels (moving average) as the detection value.
Item
Setting range
Details
Current 1 (during
Accel/Decel)
0.0 to 6,553.5 (A)
(See note 1.)
Sets the monitor value (threshold) of the output current
during acceleration or deceleration.
Current 2 (during Fre-
quency Agree)
0.0 to 6,553.5 (A)
(See note 2.)
Sets the monitor value (threshold) of the output current
during frequency agreement (while operating at con-
stant speed).
Detection Filter
Detection sensitivity
level
1 (lowest) to
level
5 (high-
est)
(See note 3.)
Sets the
level of
sensitivity to prevent detection of val-
ues that temporarily exceed the threshold value.
Status
Hold or do not hold
Selected: Status is maintained when a warning torque
is detected.
Not selected: The status is refreshed every time.
Warning Torque
Tab
Page in the Edit
Device Parameters
Window
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...