Chapter 10
10-88
Appendices
●
Alarm 2: Register Number 001A Hex
■
Inverter Monitoring: U1-
@@
12
EF7
External fault (terminal 7)
13
EF8
External fault (terminal 8)
14
---
Not used.
15
OS
Overspeed
Bit
Display
Content
0
DEV
Speed deviation
1
PGO
PG is disconnected
2 to 15
---
Not used.
Class 64
Register
number
Monitor
number
Monitored item
Output unit
Instance
Attribute
00
20
0020
U1-01
Frequency reference
Set in o1-03
00
21
0021
U1-02
Output frequency
Set in o1-03
00
22
0022
U1-03
Output current
8192 decimal = Inverter
rated current
00
23
0023
U1-04
Control method
Set in A1-02
00
24
0024
U1-05
Motor speed
Set in o1-03
00
25
0025
U1-06
Output voltage
0.1 V
00
26
0026
U1-07
Main circuit DC voltage
1 V
00
27
0027
U1-08
Output power
0.1 kW
00
28
0028
U1-09
Torque reference
0.1%
00
29
0029
U1-10
Input terminal status
Bits 0 to 7 = terminals 1 to 8
00
2A
002A
U1-11
Output terminal status
(Refer to table below.)
00
2B
002B
U1-12
Operating status
(Refer to table below.)
00
2C
002C
U1-13
Elapsed time
1 hour
00
2D
002D
U1-14
FLASH ID software No.
---
00
2E
002E
U1-15
Terminal 13 level
0.1% (100% = 10 V)
00
2F
002F
U1-16
Terminal 14 level
0.1% (100% = 20 mA)
00
30
0030
U1-17
Terminal 16 level
0.1% (100% = 10 V)
00
31
0031
U1-18
Motor secondary current
0.1% (100%: Motor rated
current)
00
32
0032
U1-19
Motor excitation current
0.1% (100%: Motor rated
current)
00
33
0033
U1-20
Output frequency after a soft
start
Set in o1-03
00
34
0034
U1-21
Input to speed control loop
0.01% (100%: Maximum fre-
quency)
00
35
0035
U1-22
Output from speed control
loop
0.1% (100%: Motor rated
current)
Bit
Display
Content
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...