Chapter 7
7-7
Configurator Settings
3.Click the
Close
Button to close the Maintenance Information Window.
Note
The setting methods used in each of the tab pages are described in the following pages.
7-1-3 Network Connection Precautions
When information is uploaded for the 3G3MV-PDRT2 and 3G3RV-PDRT2 Slaves and the DeviceNet
(Master) Unit that are connected to the network, a warning icon may be displayed under the Slave.
This icon indicates that the I/O size of the Slave and DeviceNet (Master) Unit do not match. If opera-
tion is continued without removing the cause of the warning icon, it will not be possible to see other
detected errors in the Unit status, so always use the following method to match the I/O sizes and can-
cel the warning icon.
■
Operations Using the Configurator
1.Click the right mouse button over the icon of the corresponding Slave (Inverter) in the Network
Configuration Window and select
Property
.
2.The Property Window for the 3G3MV-PDRT2 DeviceNet Communications Unit will be displayed
(the model name will depend on the type of Inverter used). Click the
I/O Information
Tab.
Click the
Get the I/O Size from the Scan List
Button and then close the window.