Chapter 3
3-22
Setup and Wiring
Switching Power Supply Configuration
Suspending the Communications Power Supply
3-3-4 Noise Prevention Wiring
• To prevent inductive noise, do not wire the communications line, PLC power lines, and other power
lines near to each other. Keep the power lines for Inverters, motors, regulators, and contactors, the
communications lines, and the PLC power lines separated from each other by at least 300 mm.
Also, provide separate conduits or ducts for the communications lines and power lines.
• Do not install communications lines and PLC power lines onto the control panel on which high-volt-
age devices are mounted.
• Because noise currents flow through metallic equipment (such as casings), the communications
cables should be placed as far away from metallic equipment as possible.
Switching power supply
AC power supply
AC input
Power
supply
circuit
DC output
Casing
S82J power supply
S82Y-
@@
N (Mounting Tool)
When using S82J power supply
DC power
supply
Insulating material (such as
baked board or acrylic board)
When using other power supplies
300 mm min.
300 mm min.
Control cable
Power cable
Ground (100
Ω
max.)
Suspended duct
Shielding
Floor duct
(1) Communications line
SYSMAC I/O Line
(2) Power line
Communications line
PLC I/O Line
PLC Power Line
General control circuit line
Low-voltage
cableCommunications
cable
(1)
(2)
(1)
(1)
(2)
(2)
Power lines
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...