![background image](http://html1.mh-extra.com/html/omron/3g3mv-pdrt2/3g3mv-pdrt2_user-manual_743559272.webp)
Chapter 10
10-14
Appendices
■
Object Details
Note 1.
The default setting for the motor's rated current depends on the Inverter model.
Example: 1.90A (0013 hex) for 200-V class, 0.4 kW
Note 2.
The figures enclosed in parentheses in the “Setting range” and “Default” columns are the
values for 400-V class Inverters.
10-2-9 Control Supervisor Objects: Class 29 Hex
Control supervisor objects are objects that have Inverter control I/O-related functions. They are
assigned according to their particular control I/O functions, such as forward operation, reverse oper-
ation, error detection, and so on. Be careful when setting up a remote I/O communications connec-
tion. These functions are shared with similar functions used for remote I/O, so even if they have been
set for message operations they may get rewritten for remote I/O.
■
Support Service Code
Instance
Attribute
Name
Content
Setting range
Default
Read
Write
Size
00
01
Object Software
Revision
Indicates class 28 soft-
ware revisions. The revi-
sion value is advanced
whenever there is a
change.
---
0001
Yes
No
Word
01
03
Motor Type
Indicates the type of motor
to be used. The setting for
a squirrel-cage inductive
motor is 7.
---
07
Yes
No
Byte
06
Motor Rated
Current
The motor's rated current
can be set and read. The
setting unit is 0.1 A. (The
setting unit can be
changed using the cur-
rent scale in Class 2A,
Instance 1, Attribute 17.)
Inverter rated
output current
10% to 120%
See note
1.
Yes
Yes
Word
07
Motor Rated
Voltage
The motor's rated voltage
can be set and read. The
setting unit is 1 V. (The
setting unit can be
changed using the voltage
scale in Class 2A,
Instance 1, Attribute 1B.)
0 to 255 V
(0 to 510 V)
(See note 2.)
00C8
(0190)
(See note
2.)
Yes
Yes
Word
Service code number (hex)
Service
0E
Get attribute single
10
Set attribute single
05
Reset attribute: Can be sent to Class 29/Instance 01
Turns OFF the Forward Operation and Reverse Operation
inputs and turns ON the Fault Reset. Then turns OFF the Fault
Reset when Inverter Ready is output.
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...