Chapter 10
10-61
Appendices
Note 1.
The values in parentheses indicate initial values when initialized in 3-wire sequence.
Note 2.
Set H5-01 to 0 to disable Inverter responses to RS-422A/485 communications.
Note 3.
Values in parentheses are for Asian model Inverters.
Note 4.
This parameter is not supported by the Asian model Inverters.
■
Protective Function Parameters
H5-04
0428
04
28
Stopping method after communication
error
0 to 3
1
3
No
H5-05
0429
04
29
Communication error detection selec-
tion
0, 1
1
1
No
H5-06
042A
04
2A
Send wait time
5 to 65
1 ms
5
No
H5-07
042B
04
2B
RTS control ON/OFF
0, 1
1
1
No
H6-01
042C
04
2C
Pulse train input function selection
0 to 2
1
0
No
H6-02
042D
04
2D
Pulse train input scaling
1000 to
32000
1 Hz
1440
Yes
H6-03
042E
04
2E
Pulse train input gain
0.0 to
1000.0
0.1%
100.0
Yes
H6-04
042F
04
2F
Pulse train input bias
−
100.0 to
100.0
0.1%
0.0
Yes
H6-05
0430
04
30
Pulse train input filter time
0.00 to
2.00
0.01 s
0.10
Yes
H6-06
0431
04
31
Pulse train monitor selection
1, 2, 5,
20, 24,
36
1
2
Yes
H6-07
0432
04
32
Pulse train monitor scaling
0 to
32000
1 Hz
1440
Yes
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
L1-01
0480
04
80
Motor protection selection
0 to 3
1
1
No
L1-02
0481
04
81
Motor protection time constant
0.1 to 5.0 0.1 min
1.0
No
L1-03
0482
04
82
Alarm operation selection during motor
overheating
0 to 3
1
3
No
L1-04
0483
04
83
Motor overheating operation selection
0 to 2
1
1
No
L1-05
0484
04
84
Motor temperature input filter time con-
stant
0.00 to
10.00
0.01 s
0.20
No
L2-01
0485
04
85
Momentary power loss detection
0 to 2
1
0
No
L2-02
0486
04
86
Momentary power loss ridethru time
0.0 to 2.0 0.1 s
Depends
on
capacity.
No
L2-03
0487
04
87
Min. baseblock time
0.1 to 5.0 0.1 s
Depends
on
capacity.
No
L2-04
0488
04
88
Voltage recovery time
0.0 to 5.0 0.1 s
Depends
on
capacity.
No
L2-05
0489
04
89
Undervoltage detection level
150 to
210 (150
to 420)
(See
note 1.)
1 V
190
(380)
(See
note 1.)
No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex)
Name
Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
Содержание 3G3MV-PDRT2
Страница 4: ......
Страница 12: ......
Страница 36: ...Chapter 1 1 22 Functions and System Configuration...
Страница 52: ...Chapter 2 2 16 Example System Startup...
Страница 94: ...Chapter 4 4 14 SYSDRIVE Inverter Settings...
Страница 130: ...Chapter 5 5 36 Remote I O Functions...
Страница 234: ...Chapter 8 8 14 Communications Errors...
Страница 362: ...R 2 Revision History...