Date
26/6/2017
Document 923860006_09_006
Document code 923860006_09_006
Page 9 from 44
2.5 Connecting the batteries
It’s recommended to use the following types of batteries:
A-1200 (12V/33Ah) and A-1202 (12V/55Ah).
Both of these types are designed for Central Battery Systems (CBS)
and the stated minimum life expectancy is at least 10 years at 20°C
ambient temperature.
First remove the battery fuse from its socket. The batteries must be
connected in series. Two cables, one red and one black can be found
in the batteries’ compartment. There is also a short cable (12cm black)
contained in the package with two hole terminals on its ends. The red
cable must be connected to the positive pole of the 1
st
battery and the
black cable must be connected to the negative pole of the 2
nd
battery.
The 3
rd
short cable must be used to connect the negative pole of the
first battery to the positive pole of the second battery.
WARNING!! Do not plug the battery fuse in this phase.
Warning!! In case of wrong battery polarity and battery fuse is
plugged in DO NOT turn off the main switch before removing the
battery fuse.
-Batteries compartment-