Date
26/6/2017
Document 923860006_09_006
Document code 923860006_09_006
Page 5 from 44
1.1 Technical Characteristics
GR-8600/300/4
GR-8600/300/8
GR-8600/600/8
Operating voltage
~230V 50-60Hz
Batteries
2 x12V/33Ah
2 x 12V/55Ah
Illumination circuits (zones)
4
8
8
Maximum AC power (input)
900VA
1.4kVA
Max. power output (emergency)
300W
600W
Max. power output (per zone)
75W
Operating temperature range
5 – 40
o
C
Degrees of cover protection
ΙΡ 21
Dimensions
67 x 50 x 27 cm
Weight (w/o batteries)
17.3kg
17.6kg
18.7kg
Battery fuse
30A/32V (maxi)
Zones fuse (output)
4A/250V (slow)
Mains fuse
8A/250V (slow)
Battery fan fuse
0.3A/250V (slow)
Type of electric shock protection
Class I
Max. operating altitude (above sea level)
1000m.
Max. relative humidity
95%
Guarantee
2 years
All fuses are size 5x20, battery fuse is 29mm car type.
WARNING
: This is a category C2 UPS product. In a residential environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
The class of Volt-meter and Ampere-meter is 1.5.