WARNING! Staircase Function works with Maintained mode only.
If
staircase function is selected in a zone, then only the
luminaries
that are set
as maintained will light in staircase function
.
Those maintained luminaries
are not lighting continuously though, but only when the staircase
switch is pressed.
In the table below you can see when a luminary is lit (supposing that the
system is in charging mode and the mains power is on)
Zone (luminaries) mode Staircase Function
Luminaries’ Light
Maintained
No
ON
Non-Maintained
No
OFF
Maintained
Yes
Only in staircase
function
Non-Maintained
Yes
OFF
It’s also important to know that staircase function and timer function is
affected by dimming level.
By selecting NO option in the staircase function, the system asks for a timer.
Timers are used to turn OFF or ON luminaries at specific hours when people
are not in the building.
Timers affect only the luminaries that are
programmed to operate as maintained
. By selecting a timer, on NO
TIMER, the zone programming is over and then the previous menu
(TECHNICIAN MENU) is shown.
(For timers programming, see par. 4.1.4)
(For programming luminaries see par. 4.1.3)
4.1.3 Programming the luminaries
In order to register and program a specific luminary manually, select the
option LUMINARIES in the TECHNICIAN MENU and press “Enter”. The
screen on the right is shown, where the system asks for a zone selection.
Select the zone that the required luminary is installed to with “Up & Down”
keys and press “Enter”.
After selecting the zone number, the system asks for the luminary’s address.
Select the required address with “Up & Down” keys and press “Enter”. The
system displays the selected zone number and luminary address for 2
seconds.
The system asks if the required luminary in that address is installed or not.
By selecting NO and pressing “Enter” the system goes back in the zone
selection. If you select YES, the system continues the luminary
programming.
Note that if you select NO for a luminary that is already installed, later in the
system screen a fault “POINT NOT REGISTERED” will be displayed. If you