Date
26/6/2017
Document 923860006_09_006
Document code 923860006_09_006
Page 15 from 44
order for the panel to be able to communicate with the luminaries. It also has
to be done when new luminaries are installed to a present system, or when
old luminaries are removed. Otherwise, manual registration is also possible
(see par.4.1.3)
The AUTODETECT LUMI/RIES procedure lasts for 75 seconds. During this
procedure the screen on the right is shown. The remaining time in seconds is
displayed too.
When the process is over, the screen on the right is shown. On the top
section of the screen, the amount of the luminaries installed in each zone
(from 1 to 8) is displayed. The total amount of all luminaries is also
displayed. Pressing “Esc” key goes back to the previous menu, or else
waiting 9 seconds goes back automatically.
Note that after this procedure every
luminary
in every zone will be set as
maintained. This way you can confirm that all illumination circuits are
working. Also, the total amount of found luminaries must match to the
luminaries installed, otherwise there has to be a connection problem.
By selecting SET BATTERY CURRENT and pressing “Enter” the screen on
the right is shown. The system begins a procedure that simulates an
emergency situation. During this procedure that lasts 90 seconds, the
luminaries installed in every zone are powered from the batteries and are lit.
The batteries’ voltage and the total current drawn by the luminaries are
displayed. This function is necessary after completing the installation and is
crucial for current fault detection.
Warning
. Before starting the procedure, the batteries of the panel must be
charged
at least to their 60% capacity
.
Warning. This procedure must be done every time a new luminary is
installed or removed, after it has first been registered in the system’s
memory.
By selecting SETUP LUMINARIES and pressing “Enter” key, the screen on
the right is shown. This option gives the ability to set all the luminaries
installed in a zone as maintained or non-maintained at once. The system
asks for a zone selection. Use the “Up & Down” keys to select the desired
zone and press “Enter”.
After selecting the required zone, the system asks for operation mode for all
luminaries in that zone. These modes are MAINTAINED or NON
MAINTAINED. After selecting an option and pressing “Enter” all luminaries
installed in that zone operate under the same mode.
This procedure is time-saving, after an auto-detection process, when one or
more zones are required to be set completely non-maintained.