5.1.2 Test
If you select TEST and press “Enter” you will see the screen on the right.
If you select MAKE A FUNCTION TEST and press “Enter” a manual function
test is conducted. Its duration is 90 seconds. The screen shows the
remaining time, the battery voltage and the discharging current that the
whole load consumes from the batteries.
When the test finishes the screen on the right is shown. The first line shows
the date and the hour of the test. The following 3 lines show the faults that
have been detected for the system, the zones and the battery. By pressing
“Esc” you return to the previous menu. If faults have been detected, then you
must go to the menu CURRENT FAULTS for more details.
If you select TEST RESULTS and press “Enter” you can see the screen on
the right.
If you select FUNCTION TEST and press “Enter” you see the screen on the
right. The first line shows the indication 01/ΧΧ (where ΧΧ the amount of tests
in memory) as well as the date and hour of the test. The following 3 lines
show the faults detected on the system zones and battery. The last line
shows the battery voltage and current at the end of the test. If more than 1
test are in memory, then using the up/down arrow keys you can view them
all.
If you select CAPACITY TEST and press “Enter” you see the screen on the
right. The first line shows the indication 01/ΧΧ (where ΧΧ the amount of tests
in memory) as well as the date and hour of the test. The following 3 lines
show the results of the test (Passed or Failed), the duration and the capacity
of the batteries. The last line shows the battery voltage and current at the
end of the test. If more than 1 test are in memory, then using the up/down