Date
26/6/2017
Document 923860006_09_006
Document code 923860006_09_006
Page 23 from 44
Select the desired date for the test using the arrow keys. The last 2 digits are
for the year. Once the required date is set, press “Enter”.
Select the hour for the test using the arrow keys.
You must select wisely the time and date of the capacity test because for the
next 12 hours after the test finishes, the system will not achieve the stated
autonomous duration due to batteries’ discharging.
4.1.12 Capacity test
By selecting MAKE A CAPACITY TEST and pressing the “Enter” key the
system conducts a manual capacity test and you see the screen on the right.
On the first line with the big letters you see the duration of the test. On the
next 3 lines you can see the voltage of the batteries, the current that
discharges the batteries and the capacity that has determined until this time.
Warning. Before starting the procedure, the batteries must be fully
charged (24h charge at least).
You can let the test to end automatically when the autonomy hits the 2/3 of
the stated autonomous duration or you can stop the test at any time by
pressing the “Esc” key.
Stated autonomous duration is set by the user. See par. 4.1.5
4.1.13 Reset Defaults
To reset all settings to factory default, select RESET DEFAULTS and press
“Enter”. When the message on the right is shown then the procedure has
finished.
4.1.14 Annual Test
If you have finished with the annual tests and want to delete the related
message, select ANNUAL TEST DONE and then press “Enter”. When the
screen shows the message on the right then the related message has been
deleted.