Date
26/6/2017
Document 923860006_09_006
Document code 923860006_09_006
Page 39 from 44
With the option PANEL SOFT VERSION, you can retrieve information
regarding the firmware installed in the panel. By pressing “Esc” you go back
to the INFORMATION menu.
By selecting TECHNICIAN INFO and pressing “Enter” you see information
regarding the name of the technician the telephone number and a general
description of the panel. This information can be changed only by using a PC
(via Ethernet). Press “Esc” to return to the INFORMATION menu.
5.1.5 Reset
By selecting RESET all current faults will be reset, including “CUTOFF TOOK
PLACE” message.
The message “CUTOFF TOOK PLACE” is displayed when there was
previously a system cutoff by low battery voltage when in emergency.
5.1.6 All Events
By selecting the option ALL EVENTS in the main menu and pressing “Enter”
you can see the screen on the right. The top screen shows the logged
information and the bottom screen shows the logged faults.
On logs containing information you can see the symbol “
i
" on the top left. On
its right with bold characters you can see the source of the event (in this case
GENERAL PANEL). Below this you can see a description of the event, the
date and time. The last line shows the number of the event to the total
number of logged events.
On logs containing faults you can see the symbol Χ on the top left. On its
right with bold characters you can see the source of the fault (in this case the
ZONE 04). Under the X you can see the name of the zone
(UNDERGROUND). Below this you see a description of the fault, the date
and time. The last line shows the number of the fault to the total number of
logged events.
With the “Up/Down” arrow keys you navigate between events. Press “Esc” to
return to the previous menu.
5.1.7 Earth Test
If you select TEST EARTH FAULT and press “Enter” you deliberately invoke
an earth fault to determine if the circuit that detects earth fault and the
indicators are operating. After the test finishes the system returns to the initial
screen.
Please be informed that when the batteries are disconnected and the battery
fuse is unplugged, the earth test will not function.