4.2.3 Programming Points
Luminaries that are addressed are also referred under the term points. By selecting the third option POINTS in the
technician menu, the page below is displayed:
Enter the zone number that the luminary is installed to and then the address. Press SETUP to continue point
programming. The page below is displayed:
First select if the point is installed or not. Select YES only for a point that is already installed, else there will be a
fault displayed. Select NO for a point that is not installed, else there will be a fault too.
Choose an operation mode for that point, MAINTAINED or NON MAINTAINED.
You can choose a name for that point too (CAPITAL ALPHANUMERIC CHARACTERS).
Select the luminary type in the dropdown list.
When done, click SAVE to store all the adjustments in the systems memory.
4.2.4 Programming the battery capacity and the autonomy
Clicking on the BATTERY CAPACITY & SYSTEM AUTONOMY you can see the following page:
Use the keyboard to write the battery capacity (33 or 55Ah). In the option SYSTEM AUTONOMY select one of the
following durations (1HOUR, 1.5 HOUR, 2 HOURS, 3 HOURS or 8 HOURS). This option DOES NOT change the
actual autonomous duration of the system. It informs the system about the minimum required autonomous
duration, so the system can determine if the required autonomy can be achieved under the capacity test, or a
power failure.
The autonomous duration when there is the maximum load installed in the system, is 1 hour. For more
duration the load must be calculated according to the system capacity.
Press the SAVE button to keep the settings in the system memory.
Clicking on TECHNICIAN MENU goes back to the technician menu page.