All connections to the illumination zones as well as any other modifications afterward require that the
mains power supply is isolated and that the battery fuse is removed
Every Zone (illumination circuit) can support up to 32 unique addressed points. Same address between two or
more points in the same zone can lead to malfunction. Point location in a row does not affect proper operation, it’s
not necessary the first point to be address #1. Maximum points table is shown below. Each line refers to zone
number and each column to point number.
Calculate the load according to the model. Do not exceed 75W per zone.
2.4 Luminary Types
The possible luminary types the system can recognize are the following:
1
NO LUMINARY
17 SPOT LIGHT 60L
2
LUMINARY 15 LED
18 SPOT LIGHT 1P
3
LUMINARY 30 LED
19 SLD-28
4
LUMINARY 3L
20 SLD-34
5
LUMINARY 6L
21 SLD-44
6
LUMINARY 4P
22 ZLD-28
7
LUMINARY 6P
23 ZLD-34
8
LUMINARY 12 LED
24 ZLD-44
9
LUMINARY 21 LED
25 DOUBLE LIGHT
10 POWER LIGHT 1 LAMP
26 ADAPTOR A
11 POWER LIGHT 2 LAMP
27 ADAPTOR B
12 EXIT SIGN
28 ADAPTOR C
13 DOUBLE EXIT SIGN
29 ADAPTOR D
14 SLIM LIGHT
30 ADAPTOR E
15 EASY LIGHT
31 ADAPTOR F
16 SPOT LIGHT 30L
32 OTHER LUMINARY