4.1.9 Inhibit mode
This option sets the INHIBIT mode ON/OFF.
About INHIBIT mode, see par. 3.
4.1.10 Programming the function test
By selecting SET FUNCTION TEST and pressing “Enter” you can set the
parameters for the automatic function test. The options are Daily, Every
Other Day or once a week on a specific day. The duration of the test is 90
seconds. During this test all the luminaries are supplied by the batteries
(simulating a power failure). Batteries’ discharge current and zones’ current
consumption are compared to the values that were logged during “SET
BATTERY CURRENT” procedure.
Select the required interval and press “Enter”.
Now set the hour for the test. With the “Up/Down” keys you can change the
value of each digit. With the “Right” key you can select next digit. To store
the time, press the right key past the last digit.
It is wise to program the function test to take place in hours and days when
the building is not crowded or even closed so it does not interfere with other
tasks. The default setting is 8:00 am every day.
4.1.11 Programming the capacity test
The capacity test procedure is able to determine if the required system autonomy can be achieved. There are 2
memory positions to adjust two different in time tests. The capacity test must be done from once every 6 months to
once a year. The capacity test lasts maximum for the 2/3 of the stated autonomous duration of the system.
By selecting SET CAPACITY TEST and pressing “Enter” you see the screen
on the right. Select the required test number, 1or 2 and press “Enter”.
By default, both tests are active. To continue select ACTIVE and press
“Enter”.