160
Malfunction report
13.1c Sensors KTY2K - Heating cont Boiler Controller (Fault 3001 to 3020) – other faults
Type of fault
Other faults
Code:
3001
HC1 Flow
X4
3002
DHW1 OnSensor
X6
3003
Outside Sensor
X2
3004
Boiler Sensor
X3
3008
TPO1
X7
3009
TPM1
X8
3011
TPU1
X9
3012
Flow Energy1
X16
3013
Return Energy1
X17
3014
ExistBoiler1
X13
3017
Cascade OnSensor
X3
3018
Cascade OffSensor
X3
3019
Circulation Return1
X14
3020
DHW1 Off Sensor
X6
Cause and Remedy:
Sensor defect
ڃ
Measure sensor (approx. 2k
ˑ
at 25°C), replace if required
Sensor cable defect
ڃ
Replace sensor
Sensor input defect
ڃ
Replace Boiler controller
13.2 Collektor sensor (Fault 1010, 2010, 3010)
Display:
[1010] Collektor BC
Description:
Collector sensor fracture, measuring circuit of collector sensor (X15) is open
Cause and Remedy:
Sensor not connected
ڃ
Check and correct wiring
Sensor defect
ڃ
Measure sensor (approx. 1,1k
ˑ
at 25°C), re-
place if required
Sensor cable defect
ڃ
Replace sensor
Display:
[2010] Collektor SC
Description:
Measuring circuit of collector sensor (X15) is shorted out
Cause and Remedy:
Sensor defect
ڃ
Measure sensor (approx. 1,1k
ˑ
at 25°C), re-
place if required
Sensor cable defect
ڃ
Replace sensor
Display:
[3010] Collektor
Description:
Other fault at input X15
Cause and Remedy:
Sensor defect
ڃ
Replace sensor
Sensor cable defect
ڃ
Replace sensor
Input on heating controller
defect
ڃ
Replace input on heating controller
PE 567 EN 1.1
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......