92
Heating Circuit
Is the opening duration of the mixer.
Note:
The relation of
mixer Open-Off—Close
allowes you to adjust the mixer to the
inertia of the hydraulic system.
is the break time of the mixer.
Note:
The relation of
mixer Open-Off—Close
allowes you to adjust the mixer to the
inertia of the hydraulic system.
Is the close time of the mixer.
Note:
The relation of
mixer Open-Off—Close
allowes you to adjust the mixer to the
inertia of the hydraulic system.
This control range starts with the
boiler temp min
and ends with the
boiler temp
min
+
controll range BT
. In the control range the switch on time of the mixer shor-
tens dynamicly. That means, the closer the boilertemp gets to the
boilertemp min
,
the shorter is the opening duration of the mixer.
This control range is operating from the calculated
flow-setpoint-temperature
up-
wards and downwards. In the control range the opening and closing duration of the
mixer are changing dynamicly to avoid a oscillation of the hydraulic system. That
means, the closer the measured flow temp is to the calculated flow temp, the shor-
ter is the opening- or closing duration of the mixer.
The minimum value of the temperature rise at the boiler sensor.
PE 567 EN 1.1
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......