Cascade settings
107
If the outside temperature falls below the
Frost Protection – Protection Temp
the
periodically Scavenging occurs according to Scavenging Time and Pause Time. De-
fault values: Scavenging Time 5min and Pause Time 60 min.
Note:
If the pump is activated because of other reasons, the Pause Time starts again.
Back to
Main menu
.
113
3..113
3..11 C
Ca
as
sc
ca
ad
de
e s
se
ettttiin
ng
gs
s
Conditions for a cascade:
• A cascade system with an accumulator is only possible with accumulator No.1.
• Exisits accumulator No.1, all participants must be assigned to accumulator No.1.
• The accumulator pump must be connected to the boiler.
Periphery Learning
Note:
Prior to the
Periphery Learning
, all participants must be connected properly.
The number of boilers and selection of the switch off sensor in a cascade system with an accumulator must
be taken in the menu Periphery Learning.
Number of Boiler
Insert the number of boilers. Peak load boilers
count to the number of boilers. Example: 3 Pelle-
matic and 1 Peak load boiler results in a number
of 4!
Switch Off Sensor
If an accumulator is present, you can choose the
TPO (AC upper sensor) or the TPM (AC middle
sensor) for the Switch Off Sensor. If there exists
no accumulator in the system, then you do not
have this choice.
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......