LED status boiler controller
19
7.3 LED status boiler controller
Display
Description
Cause and remedy
red
Power supply present
—
red flashing
Error condition
no communication possible
Check the software version
Check the bus wiring
Check the address
red / orange flashing
In the bus systems are devices using
the same address
Change the address
orange
Power supply present
Processor runs
No bus communication
Check the software version
Check the bus wiring
Check the address
orange flashing
Firmware- update is in progress
—
green flashing
Initialization (Firmware boots)
If state is unchanged, software must
be checked.
green
Operation
Cyclic communication possible
—
7.4 Cable Routing
Th cable routing and the connection of the motors and sensors is precisely described in the
Installation ma-
nual
.
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56