Malfunction report
13.7 Motor turbine (Fault 5018)
Display:
[5018] PE Motor Turbine
Description:
Vaccuum turbine not running (Exit VAK)
Cause and Remedy:
Motor unplugged
ڃ
Plug in motor, check cable connections
Motor defect
ڃ
Replace motor
Fuse F1, suction circuit
board defective
ڃ
Replace fuse
13.8 Output 230V (Fault 5019, 5022, 5023)
Display:
[5019] PE Ignition
[5022] PE Magnetic valve
[5023] PE Motor cleaning
Description:
No function of output ZUEND (Ignition)/MA (Magnetic valve)/ RM (Motor
cleaning)
Cause and Remedy:
Output unplugged
ڃ
Connect plug, check cable wiring
Current value above the
maximal Limit
ڃ
Check limits
Current value under the
minimal Limit
ڃ
Check limits
13.9 Output 230V-2 (Fault 5020, 5024, 5025, 5027, 5029, 5030)
Display:
[5020] PE Motor ashbox (Output AV)
[5024] PE Flue gas fan (Output SZ)
[5025] PE Cirkulationspump (Output UW)
[5027] PE Motor ext auger2 (Output RES2)
[5029] PE Motor boiler auger (Output ES)
[5030] PE Combustion Fan (Output LUFT)
Description:
No function of the respective motor/pump/fan
Cause and Remedy:
Motor/pump/fan
unplugged
ڃ
Connect plug, check cable wiring
Motor/pump/fan defect
ڃ
Replace motor/pump/fan
13.10 Zwischenbehälter leer - Motor res 1 (Fault 5021)
Display:
[5021] PE Hopper empty / Motor RES1 (for 36-56 kW, Pellematic Condens
or PEB)
Description:
No function of PE motor res 1
Cause and Remedy:
Motor unplugged
ڃ
Plug in motor, check cable connections
Motor defect
ڃ
Replace motor
No pellets available
ڃ
Refill storage-Room / supply tank
PE 567 EN 1.1
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......